CONNECTION OF THE ELECTRIC VALVE AND
REMOTE SENSORS
The
Beta
SE330K and SE333K control units each have two terminals (5-
6) active when closed, for connecting the following remote detectors (Fig. 3):
for METHANE gas: model SE195KM or model SE396KM.
for LPG gas: model SE195KG or model SE306KG.
If the remote sensors are not connected to terminals 5 and 6, these must
not be modified, and therefore kept disconnected at all times.
Do not forget that the electric valve must be installed on the gas pipe
outside the room to be controlled as it cannot protect against leaks upstream.
The
Beta
SE330/SE333 +
Beta
SE330/SE333 configuration is IMQ
certified.
The other configurations,
Beta
SE330/SE333 + SE195 K and
Beta
SE330/
SE333 + SE396K are not IMQ certified.
ATTENTION:
If there is a temporary loss of power during operation with
positive logic, the N.C. valve closes automatically and will need to be reset
manually when power is restored.
NEGATIVE LOGIC (SE330K):
in this case, the coil of the relay is
kept deactivated (Fig. 6).
It is perfect for N.O. (
normally open
) electric valves (Fig. 7) or N.C.
(
normally closed
) electric valves (Fig. 8).
In the event of an alarm, contacts 8 and 9 remain closed until the
alarm stops.
J2 JUMPER IN
“NEGATIVE LOGIC”
POSITION
Fig.5
7 8 9
NC C NA
J2 JUMPER IN
“POSITIVE LOGIC”
POSITION
NA
C
NC
R
R
+
-
1 2
3
5
4
6
7 8 9
SE333K
230Vac/50Hz
EV
Normally close
SE330K
NA
C
NC
R
R
+
-
1 2
3
5
4
6
7 8 9
230Vac/50Hz
EV
Normally open
Fig.6
Fig.7
Fig.8
NA
C
NC
R
R
+
-
1 2
3
5
4
6
7 8 9
230Vac/50Hz
EV
Normally close
SE330K
EXAMPLE OF APPLICATION WITH N.C. ELECTRIC VALVE SE333
Fig.4
7 8 9
NA C NC
ELECTRICAL CONNECTION WITH SEVERAL
DETECTORS:
Connection of two detectors with a single electric valve is shown in the
diagrams below. It is possible to connect more than two detectors, repeating
the same connections.
NA
C
NC
R
R
+
-
1 2
3
5
4
6
7 8 9
NA
C
NC
R
R
+
-
1 2
3
5
4
6
7 8 9
SE330K
SE330K
230Vac 50Hz
230Vac 50Hz
NO GAS GAS EV
Connection with Normally Open manual reset electric valve (with relay
normally deactivated) and a second SE330K detector.
SE330K
SE330K
SE330K
12Vdc
12Vdc
NO GAS GAS EV 12Vdc
SE330K SE396K
230Vac - 50Hz 230Vac - 50Hz
Fig. 3 Example of connection of a remote sensor.
The
Beta
SE396K detector is not IMQ certified but complies fully with
standard IEC UNI EN 50194.
POSITIVE LOGIC – NEGATIVE LOGIC
The
Beta
SE330K and SE333K gas detector can control an electric valve
using two different logics:
1 – POSITIVE LOGIC (SE333K)
2 – NEGATIVE LOGIC (SE330K)
The
J2 JUMPER
allows you to select the one required.
N.B. The J2 JUMPER is set by default to NEGATIVE LOGIC (SE330K).
N.O. manual
reset valve
POSITIVE LOGIC (SE333K):
in this case, the coil of the relay is
always live (Fig. 4) to ensure the
inherent safety
of the relay.
It is perfect for N.C. (normally closed) electric valves (Fig. 5).
In the event of an alarm, contacts 7 and 8 remain closed until the
alarm stops.
GUARANTEE CERTIFICATE
TO COMPILE AND SEND IN CASE OF DAMAGE
DEVICE: SE330KM SE330KG SE333KM SE333KG
Serial number (s.n.)_________________________________________
DEALER
Stamp:
Date of purchase:
_____/_____/_____
USER
Surname and name _________________________________________
Address _____________________________________ n°__________
Postcode ________________ Town/city ________________________
Telephone_________________________________________________
Connection with 12 Vdc Normally Open manual reset electric valve (with
relay normally deactivated) and a second SE330K detector.