background image

IST-2292.PM01.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.5/10

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

 

disconnect and connect the unit, finally try to replace a new 

“Cartridge Sensor

”. If the condition is not change, it will 

be necessary to replace the unit and/or send it back to the supplier to repair. 

All LED activate (

>24mA output signal

):

 

this happens when the “

Cartridge Sensor

” is not working or gas concentra-

tion is out of scale (higher than 100% LEL) If there are not any gas leaks and the condition is not change, it will be 
necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed according to the national dispositions in force on the safety of the plants 
and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Models TS292PG and TS292PB 

should be fixed at 20-30 cm from the floor (LPG and Petrol vapours are heavier than air). 

Models TS292PM and TS292PI

 should be fixed at 20-30 cm from the ceiling (Methane and Hydrogen are lighter than air). 

Model TS292PX 

should be fixed in high position with a gas Vapour Density less than 1 (the gas is lighter than air) or in bottom 

position with a density greater than 1, (the gas is heavier than air) (

see Table 3

 – column n.4

). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the Gas Central Unit is show 

in 

table 1

. Normally use a tree wire shielded cable. 

The terminals (+

 - S

), are plug-in type, it is necessary to extract them to make the connection. Pay attention when 

you insert them again, being polarized. With the Dip-Switches the Alarm Red Led activation is determined. 

Note:

 Dip-Switch should be set with instrument powered off. Dip-Switch 1 settled ON activates ALARM Led indica-

tion (

see Table 2

). 

Important

:

 Once installation is completed,

 it is necessary to adjust the sensor to the environment conditions,

 con-

nect the unit, wait about 20÷30 minutes and then carry out the 

”Zero Adjust” 

(see ‘

Test and Calibration >

). 

COMPATIBILITY WITH OTHER CENTRAL UNITS: In case of a central unit other then Tecnocontrol, 

please 

verify the max load resistor as shown in 

Fig. 4

. We suggest using 24Vdc power supply. 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical testing

: we advise to carry out working tests every 12 months. Tests, Zero Adjust and Calibration with 

Gas/Air mixture as explained in chapter “

Tests and Calibration

”. 

Note:

  the  detector  is  not  able  to  detect  gas  leaks  occurring  outside  the  room  where  it  is  installed,  neither  inside 

walls nor under the floor. 

Important:

 

The catalytic Pellistor sensor operates only in presence of Oxygen. Do not use pure gases or a lighter 

directly on the sensor since they could damage it irremediably. 

Warning:

 

some substances cause a permanent reduction in sensitivity. Avoid contacts of the sensor with vapours 

of Silicone compounds, Tetra-ethyl Lead (petrol antiknock additive)  and  Phosphate esters, since they can  reduce 
irremediably  its sensitivity.  Some substances  produce a temporary loss of sensitivity. This “inhibitors” include Hy-
drogen  sulphides,  Chlorine,  Chlorinated  hydrocarbons  and  halogenated  compounds.  The  sensitivity  is  recovered 
after a short period of running in clear air. 

TEST and CALIBRATION 

PAY  ATTENTION

:  This  procedure  has  to  be  made  with  extreme  attention  and  by  authorized  and  trained  people; 

because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices. 
The instrument has three different code protected functions: 

Operation Check, Zero Adjust and Calibration

.  

Operation Check, Zero Adjust and Calibration

:

 are different code protected functions. To access these functions is 

necessary  to  insert  the  relevant  “

Code

"  through  the  keys  F1s  and  F2.  To  have  the  key  pressure  recognized,  hold 

pressing  it for around a second (

until the Green Led doesn't switch off for a moment

). Then the next key can  be pressed. In 

case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Bottles

 (

for Calibration Check and Calibration

please, only

 

using a mixture 20%LEL 

(0.88%v/v)

 

Methane in Air (

20.9% Oxygen

).

 

Catalytic sensors cannot work without Oxygen

. It is possible to use 

either  the  disposable  one  litre  cylinders  with  adjust  valve  or  the  high  pressure  ones  with  reduction  gear.  Is  also 
necessary the Tecnocontrol Calibration Kit model TC011. 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having put the system in safety and inserted the "

Code Test

", all Led are switched off. Then 

they will switch on in sequence, the Led, from the yellow up to the red. At the end all the Led will remain lighted for 
around 5 seconds, then the central returns at the conditions of normal operation. It is advisable to perform this op-
eration every 6-12 months according to the use. 

Note: this function is not working if the red Led is already switched on 

 

 “ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (environment without the presence of gas or other pollutants). Immediately after having inserted the "

Zero 

Code

", as a confirmation of the operation carried out there will be 

1

 flash of the red Led and the output will become 

4,0 mA. We suggest performing this operation after the installation or after the change of the cartridge and every 6-
12 months based on the environmental conditions. 

Note

This  function  is  not  working  if  mA  output  is  more  than  5,6mA  (10%  LEL)  and/or  red  Led  is  already 

been switched on. In this case, it will be necessary to recalibrate the unit and/or replacing the “Cartridge” 

 “CALIBRATION” (

Calibration Code

: F2, F2, F2, F1, F2, F2)

this function allows completely recalibrate the sensor. 

Содержание TS292P

Страница 1: ... 20 mA lineare Linear linéaire Resistenza di carico load resistor résistance de charge 50 ohm 12Vdc 10 500 ohm 24Vdc 10 Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di risposta Response Time Temps de réponse T90 60 secondi seconds secondes...

Страница 2: ...d Rosso ALARM si accende se è stato abilitato se la concentrazione di Gas supera il 20 LIE I Guasti possibili sotto elencati sono indicati dall accensione del Led giallo FAULT e portando l uscita S a 0mA Il Led Giallo si accende ogni 4 secondi con il Led Verde acceso per avvisare che la Cartuccia Sensore ha su perato il suo limite di vita circa 5 anni e non è più garantito il corretto funzionament...

Страница 3: ...nza è automaticamente cancellata Kit di Taratura e Bombole con Miscela Aria Gas per Calibrazione e Verifica la miscela da utilizzare è Gas Meta no al 20 LIE 0 88 v v in aria 20 9 Ossigeno circa in quanto i sensori catalitici Pellistor non possono assoluta mente funzionare in assenza d ossigeno È possibile usare sia bombole monouso con valvola d erogazione sia ri caricabili ad alta pressione con ri...

Страница 4: ...M Methane CH4 is calibrated to detect Methane a gas lighter than air Its density as to air is 0 55 and its LEL Lower Explosive Limit is 4 4 v v volume TS292PG GPL is calibrated to detect LPG a gas heavier than air and consists of a mixture of 20 30 Propane C3H8 and 80 70 Butane C4H10 Propane density as to air is 1 56 while Butane is 2 05 The LEL is 1 7 v v for Propane and 1 4 v v for Butane Standa...

Страница 5: ...listor sensor operates only in presence of Oxygen Do not use pure gases or a lighter directly on the sensor since they could damage it irremediably Warning some substances cause a permanent reduction in sensitivity Avoid contacts of the sensor with vapours of Silicone compounds Tetra ethyl Lead petrol antiknock additive and Phosphate esters since they can reduce irremediably its sensitivity Some s...

Страница 6: ...olumn 8 If the result is different is necessary to recalibrate the sensor see Calibration Then close the gas bottle remove TC011 Then the mA output will slow ly decrease up to 4mA Using a cylinder with the specific gas Air mixture the output signal will correspond to the gas used Example if you have to verify a hydrogen detector using a cylinder with H2 at 0 8 v v 20 LIE in air the mA output will ...

Страница 7: ...angers d explosions et les normes de sûreté des installations Montage en Fig 1 sont indiquées les dimensions Le détecteur doit être monté en position verticale avec le capteur tourné vers le bas Positionnement du TS292PM il doit être fixé à environ 20 30 cm du plafond le gaz méthane étant plus léger que l air Positionnement du TS292PG il doit être fixé à environ 20 30 cm du plancher le gaz GPL éta...

Страница 8: ...a sortie en mA est supè riere a 10 de la LIE 5 6 mA Dans le cas il nécessaire de procéder a la calibration ou bien de substituer la car touche ETALONNAGE Code de Etalonnage F2 F2 F2 F1 F2 F1 cette fonction permet l étalonnage du capteur Le mélange à utiliser est le mélange méthane 20 LIE 0 88 v v en air 20 9 oxygène environ Durant la procédure une rare possibilité existe que la LED Jaune clignote ...

Страница 9: ... Air 1 NOTA 1 NOTE 1 REMARQUE 1 20 LIE LEL v v TESTmA TP1 TP2 mV Uscita Output Sortie mA LIE LEL TS292PM Metano Methane Méthane 1 4 4 0 55 0 88 72 7 2 20 TS292PG Butano Butane Butane 1 43 1 4 2 05 0 28 89 8 9 31 TS292PI Idrogeno Hydrogen Hydrogène 1 54 4 0 07 0 8 72 7 2 20 TS292PB Benzina Petrol Essence 0 91 1 2 2 8 0 24 89 8 9 31 TS292PX Acetato di etile Ethyl acetate 1 67 2 2 3 04 0 44 95 9 5 34...

Страница 10: ...velazione gas Gas Central Unit Centrale de détection RL S S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Dip Switch mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm Fig 4 Alimentazione Resistenza di Carico ...

Отзывы: