irremediably  its sensitivity.  Some substances  produce a temporary loss of sensitivity. This “inhibitors” include Hy-
drogen  sulphides,  Chlorine,  Chlorinated  hydrocarbons  and  halogenated  compounds.  The  sensitivity  is  recovered 
after a short period of running in clear air. 

TEST and CALIBRATION 

PAY  ATTENTION

:  This  procedure  has  to  be  made  with  extreme  attention  and  by  authorized  and  trained  people; 

because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices. 
The instrument has three different code protected functions: 

Operation Check, Zero Adjust and Calibration

.  

Operation Check, Zero Adjust, and Calibration

:

 are different code protected functions. To access these functions is 

necessary  to  insert  the  relevant  “

Code

"  through  the  keys  F1s  and  F2.  To  have  the  key  pressure  recognized,  hold 

pressing  it for around a second (

until the Green Led doesn't switch off for a moment

). Then the next key can be pressed. In 

case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Bottles

 (

for Calibration Check and Calibration

please, only

 

using a mixture 20%LEL 

(0.88%v/v)

 

Methane in Air (

20.9% Oxygen

).

 

Catalytic sensors cannot work without Oxygen

. It is possible to use 

either  the  disposable  one  litre  cylinders  with  adjust  valve  or  the  high  pressure  ones  with  reduction  gear.  Is  also 
necessary the Tecnocontrol Calibration Kit model TC011. 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having put the system in safety and inserted the "

Code Test

", all Led are switched off and all 

the  relays  are  disarmed.  Then  they  will  switch  on  in  sequence,  the  Led,  from  the  yellow  up  to  the  3°  red.  To  the 
lighting  of  the  various  Led  it  corresponds  the  activation  of  the  relevant  relays  (

relay  "FAULT"  with  the  yellow  Led,  relay 

"ALARM1" with the 1° red Led, relay "ALARM2" with the 2° red Led, relay "ALARM3" with the 3° red Led

). At the end all the Led will 

remain lighted for around 5 seconds, then the central returns at the conditions of normal operation. It is advisable to 
perform this operation every 6-12 months according to the use. 

Note: this function is not working if the 1° and/or the 2° and/or the 3° red Led have already turned on 

 

“ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (environment without the presence of gas or other pollutants). Immediately after having inserted the "

Zero 

Code

", as a confirmation of the operation carried out there will be 1 I flash of the 1° red Led and the output will be-

come 4,0 mA. We suggest performing this operation  after the installation or after the change of the cartridge and 
every 6-12 months based on the environmental conditions. 

Note

This function is not working if the 2° e/o the 3° red Led have already been switched on .In case the 1° 

red Led is already switched on only instead of flashing it will switch off for confirmation.

 

“CALIBRATION” (

Calibration Code

: F2, F2, F2, F1, F2, F2)

this function allows completely recalibrate the sensor. 

Important:

 

please, only

 

using a mixture 20%LEL (0.88%v/v)

 

Methane in Air (

20.9% Oxygen

)

 

Warning

: to guarantee that no errors of elaboration happen, the rare possibility exists that during the Calibration 

the 

yellow LED switch off every 8 seconds, 

in this case interrupt the procedure, switch off and witch on the instru-

ment and repeat the Calibration. If condition persists it will be necessary to send the detector to the supplier for the 
reparation. 

Important note:

 

During Calibration routine the mA output indicates 0mA

.

 

The Calibration can be done in clean air only (

environment without the presence of flammable or other polluting gas

). With the 

keys perform the “Calibration

 Code

 ". Wait until the Yellow and Green Led switch on fix and the 1° red Led starts to 

flash. Insert the TC011 into the sensor holder to regulate the influx of the gas the way that the flow meter indicates 
around 0.3 l/mins (

see Fig.3

). Wait around 3 minutes, then when the 3° red Led switch on (

and while it's SWITCHED ON

), 

press the key F2 on the instrument and hold it pressed until 1° and 3° Red Led are switched off for at least 2 sec-
onds (

if the 1° Red Led continue to flash, wait that the 3° Red Led switch on again and repeat the operation

). 

Then, close the gas cyl-

inder and remove TC011

. At this point we can have two possibilities: 

Yellow  and  Green  Led  illuminates:

  the  calibration  routine  has  correctly  been  performed. 

Wait  8  seconds,  until 

the instrument automatically restores the normal working conditions

(

see “Operational Description > Preheating”

Yellow LED illuminates:

 the routine has failed. In this case, wait 8 seconds, until the instrument automatically re-

peat 

Preheating

, then repeat the “

Calibration”

 routine without inserting again the code. If condition still persists after the 

replacement of the cartridge, it will be necessary to send the detector back to the manufacturer for reparation. 

“CALIBRATION CHECK” (

no Code required

)

:

 

this operation allow a real functional test of the equipment with gas

 

after the "

Calibration

" routine, or after the installation. The “

Calibration Check

” routine should be done during the pe-

riodic maintenances because this is the only method to verify the instrument real functioning. 

This routine should be done 

using a mixture 20%LEL (0.88%v/v)

 

Methane in Air (

20.9% Oxygen

Insert the TC011 over the sensor holder, adjust the sample gas bottle valve as the flow meter indicates around 0.3 
l/mins (

see Fig.3

), wait for 3 minutes and check that the instrument activates Alarms as shown in chapter “

Operational 

Description

”. 

If  the  result  is  different,  it  is  necessary  to  recalibrate  the  sensor  (

see  “Calibration”

).

 Then,  close  the  gas 

bottle, remove TC011. 

NOTE

:  further  to  the  above,  If  the  mA  output  is  also  used,  verify  with  a  voltmeter  connected  to  the  Test-Point 

TESTmA

”,

 

(

see fig.2

) the value reach the mV value as shown in 

Table 4 on column 6

 [corresponding to mA output val-

ue (

±0.2mA

) as indicated in 

column 7

T

he central unit should be display about the %LEL value (±2) as indicated in 

column 8

]. Then, the mA output will slowly decrease up to 4mA. 

Using a cylinder with the specific gas/air mixture, the output signal will correspond to the gas used. (Example if you 

have to verify a hydrogen detector, using a cylinder with H

2

 at 0.8% v/v (20% LIE) in air, the mA output will be ap-

proximately 7.2 mA (corresponding about to 72mV measured on "

TESTmA

”). 

 

Содержание SE137P

Страница 1: ...geable Uscite Outputs Sortie relè relays relais 24V 1A SPST 4 20 mA lineare Linear linéaire Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di risposta Response Time Temps de réponse T90 60 secondi seconds secondes Ripetibilità Repeatability ...

Страница 2: ...ULT Dopo circa 60 secondi il Led giallo si spegne e si accende il Led verde ON che indica il normale funzionamento Dopo questo tempo il sensore è in grado di rilevare il gas ma raggiunge le condizioni di stabilità ottimali dopo circa 4 ore di funzionamento continuo Funzionamento Normale deve essere acceso il solo Led Verde ON Il 1 Led Rosso ALARM 1 si accende se la concentrazione di Gas supera la ...

Страница 3: ...o il pavimento Importante Il sensore catalitico Pellistor funziona solo in presenza d Ossigeno Non usare gas puri o l accendino direttamente sul sensore che potrebbe essere irrimediabilmente danneggiato ATTENZIONE Considerare che in ambienti particolarmente inquinati o con vapori di sostanze infiammabili in par ticolare i solventi la vita utile del sensore può ridursi notevolmente Alcune sostanze ...

Страница 4: ...a anche l uscita in mA controllare anche con i puntali del volmetro sui Test Point TESTmA vedi Fig 2 si raggiunga il valore in mV indicato in Tabella 4 Colonna 6 ovvero che l uscita in mA au menti fino a circa il valore indicato nella Colonna 7 0 2mA e la centrale cui è collegato il Trasmettitore indichi circa il valore in LIE 2 indicato in Colonna 8 Poi l uscita tornerà progressivamente a 4 mA Se...

Страница 5: ...will be necessary to replace the unit and or send it back to the supplier to repair INSTALLATION The detector must be accurately installed according to the national dispositions in force on the safety of the plants and installation of electric devices in areas with danger of explosion Mounting The Fig 2 shows the instrument size The unit must be positioned vertically with the sensor downwards Mode...

Страница 6: ...F2 F1 F2 F2 this function allows completely recalibrate the sensor Important please only using a mixture 20 LEL 0 88 v v Methane in Air 20 9 Oxygen Warning to guarantee that no errors of elaboration happen the rare possibility exists that during the Calibration the yellow LED switch off every 8 seconds in this case interrupt the procedure switch off and witch on the instru ment and repeat the Cali...

Страница 7: ...ur catalytique Pellistor est peu sensible aux variations d humidité et température L étalonnage est effec tué pour le gaz à détecter mais en même temps l on peut détecter d autres gaz inflammables présents dans la même pièce Préchauffage a partir de la mise sous tension le détecteur commence la phase de préchauffage du capteur si gnalée par le clignotement de la LED jaune FAULT Après environ 60 se...

Страница 8: ...on 12Vcc la résistance maximale de charge RL sera de 50 Ω si on utilise une alimentation 24Vcc la RL sera de 500 Ω Fig 4 Les borniers d alimentation sont situés sur la carte principale et sont de type brochable et il est nécessaire de le débrocher pour effectuer les connexions Prêter attention en les réinsérant étant donné qu ils sont polarisés Par contre ceux des relais d alarmes montés sur la ca...

Страница 9: ... du capteur Le mélange à utiliser est le mélange méthane 20 LIE 0 88 v v en air 20 9 oxygène environ Durant la procédure une rare possibilité existe que la LED Jaune clignote chaque 8 secondes dans ce cas inter rompre la procédure puis exécutez le contrôle en coupant et en rétablissant l alimentation du détecteur En cas de persistance il sera nécessaire de remplacer et ou renvoyer le détecteur au ...

Страница 10: ...ays contacts SPST Contacts Relais 4 ALARM 1 ALARM 2 ALARM 3 FAULT OFF NA NO NA NO NA NO NC NF ON NC NF NC NF NC NF NC NF Tabella 4 Table 4 Tableau 4 ZSP05 Cartuccia Sensore Cartridge Sensor Cartouche Capteur 1 2 3 4 5 6 7 8 Modello e Gas Rilevato Model and detected Gas Modèle et Gaz détecté K LIE LEL v v Densità Densité Aria Air 1 NOTA 1 NOTE 1 REMARQUE 1 20 LIE LEL v v TESTmA TP1 TP2 mV Uscita Ou...

Страница 11: ...velazione gas Gas Central Unit Centrale de détection RL Uscita in 4 20 mA 4 20 mA Output Sortie en 4 20 mA Dip Switch Test Uscita Output Test Sortie Test 40 200mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm ...

Отзывы: