12-4. Automatic Address Setting Method
– For group control with multiple outdoor units –
Carry out automatic address setting with the remote
controller.
(1)
All auto. address operation
Press the TEST / CHK and ( ) buttons at
the same time for more than 4 seconds.
Press the SET button after confirming the CODE
No. AA (CODE No. AA: All Auto address operation).
After addressses are automatically set in order for
the outdoor units from No. 1 to No. 30, the system
returns to the normal stopped state.
(2)
Individual auto. address operation for each refrigerant
circuit.
To select each refrigerant circuit individually and
set addresses automatically, press the TEST /
CHK and ( ) buttons at the same time for
more than 4 seconds, then press the , (SET
TEMP) button once to set CODE No. A1.
(CODE No. A1: Auto. address operation)
Select R.C. No. which you want to execute the
auto. address operation with UNIT button.
Press the SET button. The auto. address operation
will start. CODE No. Changes from flashing to ON
state.
If the error is happened during the operation, the
alarm message will display. Check and remove
the cause. If you want to interrupt the operation,
press the CL button then the unit stands in waiting
mode (Press the SET buton).
If the auto. address operation finishes, the display
will disappear.
Execute the operation of the other R.C. line in the
same way by following the above steps
to
.
Complete the auto. Address operation by pressing
the TEST / CHK button.
Required time for auto. address operation:
In case of group control: a few minutes for each R.C.
NOTE
12-3. R.C. Address Setting Method
Outdoor unit R.C. address setting method
In case of group control, set the R.C. address to 1, 2, 3, … according to the No. of outdoor units.
Outdoor control PCB
CN4 (2P Black)
A. ADD (S1):
Automatic address setting start button
Used for group control (Normally, not used)
Refrigerant circuit address
(factory setting = 0)
Refrigerant circuit address (black)
: S2
Number of outdoor
R.C. address/
Position of rotary
units
outdoor unit
switch (S2 - black)
1
1
Set to 0
2
1
Set to 1
2
2
Set to 2
8
3
Set to 3
EG