User’s manual
10
UPS ERA LED 1.5 – 2-0 – 2.6
6.4
Load Control
When the Output load is higher than nominal value the UPS warns of
Overload condition
by emitting a continuous
acoustic alarm.
The UPS warns of an Overload less than 110% by acoustic alarm.
An Overload between 110% and 130% is accepted for about 30 seconds and after UPS switches automatically off.
The UPS switches immediately off if the Overload is higher than than 130%.
Once the requested power is back within range, the UPS switches automatically to the Normal mode.
Make sure that the UPS never indicates Overload condition.
Do not connect a load greater than rated value to the UPS (see POWER specifications in
the chapter “Technical Characteristics”), as this may damage the unit. In this case the
warranty is void.
6.5
Fault Condition
The UPS indicates the
Fault condition
by LCD display, by lighting of the
Fault led
and by emitting a continuous
acoustic alarm.
During Fault condition, the UPS doesn’t supply Output power and so all the supplied devices are switched off.
7
Communication Interfaces
The UPS is factory-equipped with
USB Communication Interface
. On the UPS rear side there is the connector of
the Interface.
To activate USB communication it is sufficient to connect the USB cable only.
The USB signal is isolated through photo-couplers from the dangerous voltages that are present inside the
UPS.
Connecting to the Web site
www.tecnoware.com,
it is possible to download, free of charge, the update UPS
management Software
TecnoManager
, compatible with the most popular Operative Systems.