38
BATTERY
Battery Type
12V9AH
depends on
the capacity
of external
batteries
12V9AH
depends on
the capacity
of external
batteries
12V9AH
depends on
the capacity
of external
batteries
Numbers
2
3
2
3
4
6
4
6
6
6
8
Backup time
Long run unit depends on the capacity of external batteries
Typical recharge
time(standard modle)
4 hours recover to 90% capacity (Typical)
Charging voltage
27.4 VDC ±1%
27.4
VDC
±1%
41.0
VDC
±1%
54.7 VDC ±1%
54.7
VDC
±1%
82.1
VDC
±1%
82.1 VDC
±1%
82.1
VDC
±1%
109.4
VDC
±1%
Charge current
1A
6/12A
1A
6/12A
1A
6/12A
SYSTEM FEATURES
Overload
Line
Mode
105%~125%: UPS transfer to bypass after 1minute when the utility is normal
125%~130%: UPS transfer to bypass after 30 seconds when the utility is normal
>130%: UPS transfer to bypass immediately when the utility is normal
Short Circuit
Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage
Alarm and Switch off
EPO (optional)
Shut down UPS immediately
Audible & Visual alarms
Line Failure, Battery Low, Overload, System Fault
Comunication interface
USB(or RS232), SNMPcard(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature
0
℃~
40
℃
Storage temperature
-
25
℃~
55
℃
Humidity range
20-90 % RH @ 0- 40°C (non-condensing)
Altitude
< 1500m
Noise level
Less than 55dBA at 1 Meter
PHYSICAL
Dimension W×D×H
(mm)
440*
325*
86.5
440*4
60*86.
5
440*325*
86.5
440*460*86.5
440*600*86.5
Net Weight (kg)
11.3
13.5
5.6
19.5
6.8
26.2
11
STANDARDS
Safety
IEC/EN62040-1,IEC/EN60950-1
EMC
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
* Derate to 80% of capacity when the output voltage is adjusted to 208VAC
** Derate to 75% of capacity when the Input voltage
frequency out of range(50/60
±4Hz)
*** Product specifications are subject to change without further notice.