DEVELOPMENT, MANUFACTURING AND SUPPLY OF INSTRUMENTATION
42
www.technoac.com
2. Method MIN when searching the place of damage location using sensors DKI-117
or DODK-117
When.searching.for.insulation.damages.by.«
MIN»
method,.the.contact.pins.of..DKI-117.or.
DODK-117.electrodes.should.be.placed.over.the.route,.along.the.axis.of.the.route..When.you.
use.the.MIN.method,.the.signal.increases.smoothly.at.first,.then.rapidly.decreases.to.a.certain.
minimum.value,.then.as.the.distance.from.the.damage.place.increases,.it.rises.sharply.again.and.
then.gradually.decreases.
The.place.of.damage.will.be.located.midway.between.the.electrodes,.at.a.time.when.the.signal.
reaches.the.minimum.value.
(fig. А.2).
The. sensor. DODK-117. provides. a. «fast». method. of. damage. location,. which. is. especially.
important.for.the.extensive.communications,.and.the.sensor.DKI-117.provides.a.higher.sensitivity.
and.accuracy.of.damage.location.and.needs.only.one.operator.for.work.with.it.