65
Not possible to manually switch an output:
If the output has speed control (A1, A2, A6 or A7) and is actually set to speed control, pay at-
tention to the speed stage when using manual mode. Set to stage 30 when testing the pump's
basic function.
Electronic pumps
cannot
be operated speed-controlled due to their internal structure. Con-
nection to one of the outputs A1, A2, A6 or A7 as a
switch output
is possible. However it is
recommended to connect these pumps to one of the relay outputs (A3 - A5, A8 - A11).
If a valve or contactor is to be triggered using a speed-controlled output (also along with a
pump), the parameters for this output have to be set as a switch output because the speed
control cannot work on such a consumer!
Speed-controlled outputs may not be able to switch
small loads
reliably (< 5 W, such as
valves, contactor, etc.). This is especially true for output A1 with its integrated power line filter,
which can only be operated with a minimum load
≥
20 W. If the speed-controlled outputs (A2,
A6, A7)
only
control small loads, an additional parallel load or the subsequent RC component
is necessary to make switching reliable (available as a special accessory)
Make sure that outputs 5, 12, and 13, are potential-free and do not have power. It is thus only
possible to directly switch a 230V consumer when the proper wiring has been made.
If it is not possible to switch an output on or off in manual mode because the cursor could not
be positioned next to the proper parameter, there are the following two options:
o
A message is currently active and switches the relative output dominant ON or OFF (dis-
play of message in the function overview). In this case, manual mode is not possible.
o
An expert has set the setting User interlock (outputs) to yes. By this, only experts can man-
ually operate the outputs.
Troubleshooting - hardware
If the cause of the error is clearly defective hardware, please send the equipment to your retailer or
manufacturer for repairs. Please do not forget to describe the error when sending back the device
(simply saying "the device does not work, please repair" is insufficient). Only then can the control
system be repaired quickly and inexpensively.
Troubleshooting - programming
The manufacturer can help you find a remedy if the proper documentation and data are provided. The
following are indispensable:
A hydraulic diagram by fax (best option) or e-mail (WMF, JPG, ENG)
Complete programming by means of TAPPS files or, at least, the function data by e-mail
Operating system version for the control system
All existing LOG files or at least the (temperature) values of the inputs at the time the system
malfunctioned
A telephone call to describe the problem - a written description of the error does often not suf-
fice, and the manufacturer cannot accept it.
Contactor
100nF/630V 100R/0,5W
A1
N
UVR1611
Содержание UVR1611K-N-D
Страница 2: ......
Страница 50: ...Installation instructions 50 Dimensioned drawings External dimensions mounting base ...