21
Technical data RSM610
Subject to technical modifications.
© 2020
All
inputs
Temperature sensors of type PT1000, KTY (2 kΩ/25 °C), KTY
(1 kΩ/25 °C), PT100, PT500, Ni1000, Ni1000TK5000 and room sen
-
sors RAS or RASPT, radiation sensor GBS01, thermocouple THEL,
humidity sensor RFS, rain sensor RES01, pulses
max. 10 Hz
(e.g. for
flow rate transducer VSG), voltage
up to 3.3 V DC
, resistance
(1-100 kΩ), and as a digital input
Inputs 4, 5
Auxiliary voltage (0-10 V DC)
Input
6
Also pulse input
up to 20 Hz
, for flow rate transducer VSG or S0 sig
-
nals, for example
Outputs 1 - 5
Relay outputs, partially with N/O contacts
Output 6
Relay changeover contact –
potential-free
Outputs 7 - 10
Analogue outputs 0-10 V (max. 20 mA) or PWM (10 V/1 kHz), or
expansion option as switching outputs with auxiliary relay modules
Output 7
RSM610-A24, -MB24
Supply for external 24 V devices, max. 6 W
in total
along with the
12 V devices
Output 9
RSM610-MB, -MB24
M-Bus input for up to 4 M-Bus meters
Max. breaking capacity
Relay outputs 230V / 3A each
Max. bus load (DL bus)
100%
CAN bus
Standard data rate 50 kbit/s, adjustable from 5 to 500 kbit/s
M-Bus
RSM610-MB, -MB24
Standard baud rate 2400 Bd; adjustable from 300 to 38,400 Bd; data
from max. 4 M-Bus devices can be read
12V
Power supply for external devices, max. 6 W
in total
Differential temperatures With separate start and stop differential
Threshold values
With separate start and stop differential or fixed hysteresis
Temperature measuring
range
PT100, PT500, PT1000: -200 °C to +850 °C with a resolution of 0.1 K
All other temperature sensors: -49.9 °C to +249.9 °C with a resolution
of 0.1 K
Temperature accuracy
Typ. 0.4 K, max. ±1 K within a range of 0 - 100 °C
for PT1000 sensors
Resistance accuracy
max. 1,6% at 100kΩ (measured variable: Resistance, process vari
-
able: Resistance)
Voltage accuracy
Typ.1 %, max. 5 % of maximum input measuring range
Output 0-10V accuracy
Max. -2% to +6%
Connection
100 - 230 V, 50 - 60 Hz, (outputs A1 – A5 and device are fused jointly
with 6.3 A (fast))
Supply cable
3 x 1 mm² H05VV-F to EN 60730-1 (cable with standard plug included
in the standard sensor pack)
Power consumption
1.0 – 1.9 W, subject to the number of active switching outputs
IP rating
IP40
Protection class
II – double insulated
Permissible ambient
temperature
+5
to
+45°C