3.3 - CONDENSATES

• Both horizontal and vertical units come equipped with a condensate drainage connection.
• On all vertical models, the auxiliary condensate tray (accessory) can be placed underneath the hydraulic connections to

recover condensate water which may form on valves and piping.

• In all cases, the condensate drainage installation must respect certain criteria:

- provide at least a 3 % slope from the fan coil unit,
- install a trap to avoid unpleasant odors,
- do not immerse the end of the drainage tube,
- do not bend the drainage tube.

• As  the  units  are  not  fitted  with  a  condensate  pump,  they  must  be  installed

accordingly.

• If  a  centralized  evacuation  for  several  units  is  used,  the  system  must  be  fitted

with an air vent to avoid pressurization of the condensate tube and back flow of
condensate  toward  the  units.  The  diameter  of  the  condensate  line  must  be
calculated with relation to the total output of condensate.

Trap

Slope

Condensate discharge pipe

Immersion

4 - STARTING

4.1 - PRELIMINARY CHECKS

4.1.1 - MAKE SURE

• That the unit is well fixed.
• That  the  power  cables  are  well  fixed  to  their  connection  terminals.  Loose  terminals  can  cause  heat  build-up  on  the

terminal board.

• That the electric cables are properly insulated from any pieces of sheet or metal parts which could damage them.
• That the unit is connected to earth.
• That no tools or any other objects have been left in the unit.
• That the filter is correctly fitted.
• The coil box is clean.
• That the condensate discharge outlet is correctly connected.
• The condensate drain pan is clean.
• Using a bottle, pour water into the condensate recovery tray to ensure that drainage is carried out properly.
•  The  water  connections  are  positioned  correctly  and  tightened  (ensure  that  the  valve  kit  connections  are  properly

tightened).

• That the casing is properly reinstalled (for appliances with body panels) and that the access doors are locked if the built-

in control is not installed.

4.1.2 - SWITCH ON THE UNIT

• Using the isolation and protection device.
• Start the appliance by using the control box.
• Make sure that the fan functions correctly at the three fan speeds, without abnormal mechanical noise (two speeds only

for ducted units).

4.1.3 - FILL THE HYDRAULIC CIRCUIT WITH WATER

• If a control valve is assembled, make sure that it is in open position before filling the exchanger.
• Check that all the connections are watertight.
• Proceed with draining the appliances.

4.2 - PURGING THE FAN COIL UNIT

• The  air  outlet  plug  and  drain  plug  are  located  at  the  level  of  the  water

connections (see drawing opposite).

NOTE:

- Never unscrew these plugs by more than 3 mm or three turns.
- Air release: top point of the coil box.
- Drain: low point of the coil box.

IMPORTANT

Before doing any work on the installation, make sure it is switched off and put out of bounds.

max

 3 m

m

Positions of the air
release and drain
plugs.

Содержание TWN Series

Страница 1: ...tiLocoNVettoRe VeNtiLo coNVectoRes VeNtiLatoRKoNVeKtoReN Janvier 2013 10 11 489 F GB I E D 03 Etiquette signal tique f gb i e d Notice d iNstaLLatioN iNstaLLatioN iNstRUctioN MaNUaLe d iNstaLLaZioNe M...

Страница 2: ...ed out by gravity To ensure the removal of condensate by gravity the appliance must be assembled horizontally or slightly tilted towards the outlet side see paragraph 3 3 The fan speed switches can on...

Страница 3: ...nage tube vertical models Fit the tube on the opposite side do not forget to reverse the position of the plugs located at each end of the tray Replace the grommet f pass the motor cable through the gr...

Страница 4: ...l Cv models only NOTE For false ceiling applications the installation s maximum heights must be respected in order to avoid problems related to stratification Such problems are best controlled by plac...

Страница 5: ...ION OF PIPES The insulation concerns the water return and inlet pipes Use polyethylene sheathing at least 9 mm thick After connection and leak inspection insulate the unit s valves tubes and connectio...

Страница 6: ...ied separately refer to the kit s installation instructions 3 2 3 REMOTE CONTROLS ACCESSORIES 5 types RAB 30 code 70250076 with manual change over cooling heating switching for 2 pipe or 4 pipe or 2 p...

Страница 7: ...he settings on DIP switches 1 to 8 located inside the control depending on the application refer to the indications below and the controller s technical manuals B Connections with manual remote contro...

Страница 8: ...ning the operation of this controller consult Technical Instructions No 10 12 152 TWN 70250051 N U L N Y11 4 GV MV PV Q1 Q2 Q3 8 9 10 M B2 B1 D1 GND TWN 70250051 N U L N Y11 4 GV MV PV Q1 Q2 Q3 8 9 10...

Страница 9: ...1 5 mm2 To avoid electromagnetic disturbance do not route sensor connection next to power cables Temperature sensor bare for RCC remote controls code 70250053 Type CTN 3 k at 25 C IP 65 cl II 2 uses p...

Страница 10: ...d in this manner must come from the same source The polarities must be strictly respected Maximum total connection length 80m with 1 5 mm2 As the sensor inputs are connected to 230 v use a contact and...

Страница 11: ...to earth That no tools or any other objects have been left in the unit That the filter is correctly fitted The coil box is clean That the condensate discharge outlet is correctly connected The conden...

Страница 12: ...condition of the appliance regularly and clean the coil as well as the condensate drain pan Both sides of the coil must be cleaned by using a vacuum cleaner with a rubber end piece and by taking care...

Страница 13: ...GB 13...

Страница 14: ...F GB D I E...

Страница 15: ...ateriali e componenti di alta qualit che sono riutilizzabili o riciclabili Alla fine della sua vita utile deve essere smaltito separatamente dai rifiuti domestici Vi preghiamo di smaltire questo appar...

Страница 16: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Отзывы: