background image

GB

2

SUMMARY

1 - GENERALITIES

1.1 - GENERAL SUPPLY CONDITIONS

• Generally speaking, the material is transported at the consignee’s risk.
• The consignee must immediately provide the carrier with written reserves if he finds any damage caused during transport.

1.2 - RECOMMENDATIONS

• Prior to all servicing or other actions on the equipment, installation, commissioning, operation, or maintenance, the

personnel in charge of these operations shall become familiar with the instructions and recommendations provided in the
installation manual of the unit as well as the elements of the project's technical file.

• The personnel responsible for receiving the unit must conduct a visual inspection in order to identify all damage to which

the unit may have been subjected during transport: refrigerating circuit, electrical cabinet, cassis and cabinet.

• The unit must be installed, started, maintained, serviced by qualified and authorised personnel, in compliance with the

requirements of all directives, laws and regulations and in accordance with standard trade practices.

• During installation, troubleshooting and maintenance operations, the use of pipes as a step: under the stress, the pipe may

rupture and the refrigerant may cause serious burns.

MARKING 

This product marked 

conforms to the essential requirements of the Directives:

- Low voltage no. 2006/95/EC.
- Electromagnetic Compatibility no. 89/336 EEC, modified 92/31 and 93/68 EEC.

R 407 C

• Fluid R 407 C is not a pure fluid but a blend composed of:

-  23% R 32 + 25% R 125 + 52% R 134 A.

• The compressors approved for operation with this fluid are

filled beforehand with polyalcohol oil. 
Contrary to mineral oil, it is very hygroscopic: it absorbs the
humidity of the ambient air very quickly. This can modify its
lubricant properties and lead in time to the destruction of the
compressor.

MAINTENANCE INSTRUCTIONS

1

- Never add oil to the appliance; the compressor is filled

with polyalcohol oil, a special oil which cannot tolerate the
presence of other oils.

2

- The instruments used for:

- filling,
- pressure measurements,
- emptying under vacuum,
- recovering the fluid,

must be compatible and only used for the R 407 C fluid.

3

- The weight of the refrigerant contained in the storage

bottle must be checked constantly. Do not use it from the
moment the remaining weight is less than 10% of the total
weight.

4

- In the case of a new charge:

- do not use the charging cylinder,
- use a balance and a dip pipe type R 407 C cylinder,
- charge the weight of R 407 C as per the value indicated

on the unit’s identification plate,

- IMPORTANT: see instruction 3 above.

5

- The charge 

must

be undertaken in liquid phase.

6

- In case of leakage, do not complete the charge:  recover

the remaining refrigerant for recycling and perform a total
charge.
Recovery, recycling or the destruction of the fluid must be
done in compliance with the laws in force in the country
concerned.

7

- If the refrigerant circuit is opened, you must:

- avoid the entry of air into the circuit as much as

possible,

- replace the filter drier,
- perform the "vacuum operation" at a minimum level of

0.3 mbar (static)

.

8

- Do not release R 407 C fluid into the atmosphere. This

fluid is a fluorinated greenhouse gases, covered by the
Kyoto Protocol with a Global Warming Potential 
(GWP) = 1653 - (EC Directive 842 / 2006).

APPLIANCES FILLED WITH R 407 C

1 - Generalities  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 - Presentation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 - Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 - Connections  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5 - Operation of "ECH" electronic control . . . . . . . . . . . . . . . . . . . . . . 6
6 - Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 - Starting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 - Maintenance instruction  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 - Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

10 - Circulator curves  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

11 - Pressure tables  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

12 - Wiring diagrams  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

 

Содержание PHT 13

Страница 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Страница 2: ...humidity of the ambient air very quickly This can modify its lubricant properties and lead in time to the destruction of the compressor MAINTENANCE INSTRUCTIONS 1 Never add oil to the appliance the c...

Страница 3: ...lation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people including child...

Страница 4: ...st not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan project...

Страница 5: ...he table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 100 POWER SUPPLY CABLE Section see tabl...

Страница 6: ...f a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a printed circuit board o...

Страница 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Страница 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Страница 9: ...tions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons...

Страница 10: ...tor lamp 7 Note The ventilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be...

Страница 11: ...a time delay system in order to respect a maximum number of starts per hour 10 a minimum stop time Cycle inversion valve The valve is actuated during defrost cycles Control hysteresis See the operati...

Страница 12: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Страница 13: ...nal exchangers casings and the cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by...

Страница 14: ...n the spare parts list for replacing defective refrigeration components Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735 1 Leak detection in the case of pressure tes...

Страница 15: ...8 16 4 14 4 51 4 59 19 64 23 70 26 19 17 4 20 4 60 4 69 19 67 23 70 26 19 18 4 25 4 69 4 78 19 70 23 70 26 19 19 4 31 4 79 4 88 19 73 23 70 26 20 20 4 36 4 88 4 97 19 77 23 70 26 20 21 4 40 4 93 5 02...

Страница 16: ...4 53 4 76 20 08 23 98 26 56 17 4 28 4 62 4 85 20 09 23 98 26 55 18 4 36 4 71 4 94 20 10 23 98 26 53 19 4 43 4 79 5 03 20 12 23 98 26 52 20 4 51 4 88 5 12 20 13 23 98 26 50 21 4 55 4 92 5 16 20 13 23...

Страница 17: ...apacitor C11 M11 capacitor C3 Filter E1 High pressure switch E2 Low pressure switch EV1 Electrovalve J1 Water differential pressure switch KA1 Phase sequence controller KM2 Contactor compressor KM3 Ci...

Страница 18: ...F GB D P I E...

Страница 19: ...F GB D P I E...

Страница 20: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Отзывы: