65
E. Check negative phase relay.
F. Check magnetic contactor.
G. Check indoor PCB Ass'y.
H. Check compressor motor protector.
Check negative phase relay to see
if it has operated.
•
Rewire power supply wires.
•
YES
(47C)
Check coil resistance of magnetic
contactor.
•
(MG)
YES
Check compressor motor
internal protector.
•
(49C)
Temperature of compressor is
abnormally high.
Refrigerant gas shortage.
YES
YES
Charge refrigerant gas.
Check compressor.
There is a possibility of
locked rotor.
•
NO 90% or more of
rated voltage.
NO
It’s operated.
Check compressor motor
overcurrent relay. (51C)
•
Clean heat exchanger or
remove obstacles.
•
Check power supply voltage.
Voltage is abnormally low.
•
Outdoor heat exchanger coil
is dirty or there are obstacles
near air suction inlet.