background image

25

9-4-9. Electric expansion valve

  When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions. Labels are 

applied to the valve body and coil, corresponding to the connector colors, to identify them.

*

 If you have manually checked the electric expansion valve, be sure to reapply the outdoor 220 V after you have replaced the 

wiring. (The position of the electric expansion valve will be changed.)

9-4-10. Branch tubing temperature sensor

Check that the sensor is securely contained in the thermostat holder.

9-4-11. Breaker

Check whether or not the breaker has been tripped.

  Check that the breakers and fuses used are of the specified capacity.

  Check that the breaker and its line are exclusive for A/C use. 

9-4-12. Refrigerant gas pressure

Start a COOL test run, and measure the temperatures of the A/C intake air and discharge air. Compare the values with the 
performance charts.

  If the values are higher than the performance charts: 

Check for refrigerant shortage or blockage of the refrigerant circuit.

 

Assessment of refrigerant shortage:

a

  The low-pressure pressure value is 5 MPa or more below the value in the performance charts.

b

  There is little condensation on the indoor heat exchanger, which overall appears dry.

 

Distinguishing between refrigerant shortage and refrigerant circuit blockage:

 

If the low-pressure pressure does not change when the circuit is charged 2–3 times with refrigerant gas (200 g each time), 
or if the change is small, then the problem may not be refrigerant shortage. The problem may be a blockage of the 
refrigerant circuit.

a

  Check that there is no internal leakage inside the 4-way valve:

 

At the low-pressure side tubing, check that there is no temperature difference between the intake and discharge of the 
4-way valve.

b

  Check that the electric expansion valve is not blocked. Check as described on the preceding page.

NOTE:

  Cool the main unit with 

a damp cloth or other 
means while welding.

  When applying 

vacuum, use the 
special service magnet 
and rotate at least 5 
revolutions 
counterclockwise to 
fully open the electric 
expansion valve.

Use a tester to measure the voltage (12 V).

  When the power is turned ON, the needle will move from 

MMV (white) 

 MVA (black) 

 MVB (red) 

 MVC (blue) 

 

MVD (yellow)  in sequence in approximately 10 – 20 seconds 
for each point.

Controller check

No voltage on circuit board

Voltage varies

No temperature change

Temperature changes

0

Approx. 46 

±

 4

Check the coil resistance.

Replace the coil.

Replace the electric 

expansion valve.

This part is normal. 

Check elsewhere.

Check the illumination 

of the red LED.

Check the resistance between the 

gray lead wire and the other wires.

Resistance is OK if it is 46 

±

 4

 at 20

°

C.

Use the special service magnet 
and rotate 5 revolutions 
clockwise to fully close the valve. 
Then start the unit and measure 
the temperatures at the inlet and 
outlet tubes of the electric 
expansion valve. If the 
temperature difference is large, 
the valve is closed. 
Then rotate 5 revolutions 
counterclockwise to open the 
valve. Operation is normal if the 
temperature difference between 
the 2 tubes drops.

Replace the controller.

Open and close the 

electric expansion valve 

by hand to check it.

*

Содержание GRF314M35IAA

Страница 1: ...ecial attention when servicing the unit 4 room multi Outdoor unit Combined Indoor Units 1 How these units may be combined is given in the Unit Combination Tables in the Appendix 2 Be sure to operate t...

Страница 2: ...ng Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air...

Страница 3: ...rrent Control 18 8 3 Low Start Current 18 8 4 Compressor Temperature Control 18 8 5 Outdoor Fan Control 18 8 6 Control at HEAT Start up 19 9 TROUBLESHOOTING 9 1 Conditions That Do Not Represent Troubl...

Страница 4: ...RANGE Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Maximum 32 C D B 23 C W B 43 C D B Minimum 19 C D B 14 C W B 19 C D B Heating Maximum 27 C D B 24 C D B 18 C W B Minimum 16 C...

Страница 5: ...m in 6 35 1 4 4 tube diameter Wide tube mm in 9 52 3 8 3 mm in 12 7 1 2 1 Dimensions Weight Unit dimensions Height mm 880 Width mm 940 Depth mm 340 Package dimensions Height mm 981 Width mm 1 016 Dept...

Страница 6: ...control YES Compressor discharge temp control YES Operation cut off control in abnormal ambient temp Run capacitor F VAC Crankcase heater 25W 240V Fan Fan Motor Type Propeller Q ty Dia mm 1 460 Fan m...

Страница 7: ......

Страница 8: ...18 880 940 33 7 Wide tube service valve 9 52 3 8 Wide tube service valve 12 7 1 2 Narrow tube service valve 6 35 1 4 336 256 416 176 25 13 380 AIR DISCHARGE 25 13 465 Unit mm 25 25 10 405 13 13 660 1...

Страница 9: ...n accumulator Receiver tank Indoor unit Insulation of Refrigerant Tubing Because capillary tubing is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To prev...

Страница 10: ...fan 2 Operating current performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 1 High pressure performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Operati...

Страница 11: ...erformance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 1 High pressure performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Operating current A Low pressure...

Страница 12: ...fan 2 Operating current performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 1 High pressure performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Operati...

Страница 13: ...erformance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Low pressure MPa High pressure MPa Operating current A Indoor discharge air temperature C Indoor discharge air t...

Страница 14: ...PE THERMISTOR ROOM B NARROW PIPE TH6 MECHANICAL VALVE MVA MVD BOARD IN WIRE DEFROST VALVE DEF CONTROL PCB M U L T I P L E I N D O O R U N I T S H E A T P U M P O U T D O O R U N I T F O R F O U R R O...

Страница 15: ...above or below the outdoor unit and within a total tubing length L1 L2 L3 L4 from the outdoor unit as detailed in Table 1 and Fig 1 INDOOR UNIT 1 INDOOR UNIT 4 INDOOR UNIT 3 INDOOR UNIT 2 Tubing leng...

Страница 16: ...oor unit Union 12 7 Flare 9 52 12 7 D 12 7 9 52 Optional parts STK 43TCA 94 124 types 94 124 types 94 124 types 18 type More than 17 m 2 Connecting indoor unit type 184 at D Length of tube more than 1...

Страница 17: ...nd that will not magnify operating noise or vibration Fasten in place with the anchor bolts M10 provide a base using concrete or similar material and ensure proper drainage select a location where the...

Страница 18: ...o maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In principle the top direction should be unobstructed...

Страница 19: ...it B Unit A Unit C Unit D Unit B Unit C Unit D A Terminal plate 16P Grounding line Power supply Single phase AC 220V 240V B Terminal plate 3P CAUTION Be sure to connect the power supply line to the ou...

Страница 20: ...ure is less than 0 C Compressor 100 Hz operation 4 way valve ON Outdoor fan OFF Solenoid valve ON for hot gas bypass Indoor fan OFF Temperature of the outdoor heat exchanger is at or above the tempera...

Страница 21: ...nt control The operating frequency upper limits shown in the figure below are established for frequency reduction and increase prohibit Example of operation for heating Example of operation during coo...

Страница 22: ...ecrease Stop operation 58 54 60 Fan H Fan H Fan H Fan L Fan L Fan L Less than 35 Hz Above 35 Hz Above 5 C 5 C or below Outdoor air 5 C 19 Hz Frequency 8 6 Control at HEAT Start up If HEAT operation is...

Страница 23: ...oximately 60 seconds will be required for the charge to dissipate However allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble with the outdoor control circuit...

Страница 24: ...ing D sensor narrow tubing Outdoor air temperature sensor Branch tubing A sensor wide tubing Branch tubing B sensor wide tubing Branch tubing C sensor wide tubing Branch tubing D sensor wide tubing CT...

Страница 25: ...NOTE The dashed line for the defrost or clean defrost lamp indicates lamp illumination at clean defrost only The maximum length of defrost operation is 12 minutes Defrost can also be ended based on t...

Страница 26: ...Compressor Compressor protective thermistor Outdoor fan motor 4 way valve Coil thermistor Electric expansion valve Branch tubing temperature sensor Breaker Refrigerant gas pressure Measure during a te...

Страница 27: ...and If the fan rotates easily a Replace the running capacitor on the outdoor control circuit board b Check for an open circuit in the fan motor coil winding c Use the tester AC range to check whether...

Страница 28: ...n the problem may not be refrigerant shortage The problem may be a blockage of the refrigerant circuit a Check that there is no internal leakage inside the 4 way valve At the low pressure side tubing...

Страница 29: ...T h g i h e r a s e r u t a r e p m e t r o o d t u o d n a r o o d n i e h t f I y n a g n i p p o t s s e t a v i t c a f f o t u c k a e p t n e r r u c e h t y c n e u q e r f n i s e s a e r c n...

Страница 30: ...t s o r f e D N O s n r u t n a f r o o d n I r o f e v l a v d i o n e l o s e h t s d n o c e s 0 1 r e t f A F F O s n r u t s s a p y b s a g t o h d e r a e p p a s i d s a h l e e f r i a d l o...

Страница 31: ...h t s e t u n i m 3 r e t f A y l l a c i t a m o t u a g n i t a r e p o s i e c n a l a b e r u s s e r p a s e t u n i m 3 e s e h t g n i r u D t r a t s o t r o s s e r p m o c e h t g n i w o l...

Страница 32: ...a m n o i t a r e p o A Y R D n e e w t e b s e g n a h c n a f r o o d n i e h T Low and LL very low over a 6 minute n o i t a r e p o n a f n o i t a u t c u l f f 1 s i s i h T e l c y c g 2 below...

Страница 33: ...at its normal mixed composition state in liquid phase When refrigerant R410A is used the composition will differ depending on whether it is in gaseous or liquid phase and the basic performance of the...

Страница 34: ...g R22 and R407C No addition of compressor oil for R410A No additional charge of compressor oil is permitted No use of refrigerant other than R410A Never use a refrigerant other than R410A If refrigera...

Страница 35: ...ging cylinder Refrigerant recovery unit Vacuum pump with anti reverse flow 1 Solenoid valve installed type which prevents oil from flowing back into the unit when the power is off is recommended Vacuu...

Страница 36: ...lve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be dam...

Страница 37: ...6Kg using a capacity of a 10Kg cylinder the minimum necessary amount for the cylinder is 0 76 10 0 20 2 76Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer If...

Страница 38: ...refrigerant other than R410A Also do not use oxygen or any flammable gas 5 Evacuation Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due...

Страница 39: ...0 76Kg using a capacity of a 10Kg cylinder the minimum necessary amount for the cylinder is 0 76 10 0 20 2 76Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer...

Страница 40: ...nt R410A for existing units which use R22 This will cause the air conditioner to operate improperly and may result in a hazardous condition 10 8 2 Use of Existing Tubing If replacing an older unit tha...

Страница 41: ...ES APPENDIX Be sure to operate the air conditioning system only when 2 or more indoor units have been installed If operated with only a single unit installed the returning fluid to the compressor may...

Страница 42: ...Max Min Max 2 8 2 8 Heating 4 00 4 00 8 0 2 030 9 3 1 6 9 0 800 2 170 Cooling 2 80 2 80 5 6 1 710 8 1 1 1 6 7 540 1 870 2 8 3 6 Heating 4 00 4 80 8 8 2 090 9 4 1 7 9 0 820 2 170 Cooling 2 80 3 60 6 4...

Страница 43: ...90 3 55 3 55 10 0 2 170 9 7 1 7 10 8 820 2 350 Cooling 2 50 3 25 3 25 9 0 1 940 8 8 1 2 10 5 620 2 380 3 6 3 6 3 6 Heating 3 33 3 33 3 33 10 0 2 170 9 7 1 7 10 8 820 2 350 Cooling 3 00 3 00 3 00 9 0...

Страница 44: ...0 9 0 1 940 8 8 1 2 10 5 620 2 380 2 8 3 6 Heating 2 20 2 60 2 60 2 60 10 0 2 170 9 7 3 6 3 6 1 7 10 8 820 2 350 Cooling 1 80 2 40 2 40 2 40 9 0 1 940 8 8 1 2 10 5 620 2 380 2 8 2 8 Heating 2 00 2 00...

Страница 45: ......

Отзывы: