4.  Air Purging

Air and moisture remaining in the refrigerant system

have undesirable effects as indicated below. There-

fore, they must be purged completely.

pressure in the system rises

operating current rises

cooling efficiency drops

moisture in the air may freeze and block capillary

tubing

water may lead to corrosion of parts in the refriger-

ant system

Air Purging with a Vacuum Pump 
(for Test Run)

In order to protect the earth’s environment, be sure to

use a vacuum pump to perform the air purge.

(Never perform an air purge by using the refrigerant

gas cylinder or other external gas, or by using the gas

inside the outdoor unit.)

For GRF194MR5IAA, perform the air purge for tubes A

and B. For GRF244MR5IAA, perform the air purge for

tubes A, B, and C. Use the same procedures for all

tubes.

(1) Check that each tube (both narrow and wide

tubes) between the indoor and outdoor units have

been properly connected and all wiring for the test

run has been completed. Note that both narrow

and wide tube service valves on the outdoor unit

are kept closed at this stage.

(2) Using an adjustable wrench or box wrench,

remove the valve caps from the service valve on

both narrow and wide tubes.

(3) Connect a vacuum pump and a manifold valve

(with pressure gauges) to the service port on the

Hi

Lo

B

A

C

Service valve 
on narrow 
tube side

Service 
valve on 
wide tube 
side

With push-pin

Hex wrench 
(nominal size 4 mm, not provided)

Manifold gauge 
(special for R410A)

Low-
pressure 
valve

Open

Charging hose
(special for R410A)

Leave the 
valve open.

Vacuum pump 
adapter 
(for preventing 
reverse flow)
(special for 
R410A)

Vacuum 
pump

High-pressure valve

Fig. 20

Cap tightening torque:
20   25 N-m
(200   250 kgf-cm)
(Tighten by hand, then 
use a wrench to turn.) 

Stopper

Spindle

Screw diameter: 1/2
UNF 20 threads

Valve core

Cap nut tightening torque:
7   11 N-m
(70   110 kgf-cm)
(Tighten by hand, then use a 
wrench to turn approximately 30 .)

<Structure of service valve on wide tube side>

Fig. 21

CAUTION

Be sure to use a manifold valve for
air purging. If it is not available,
use a stop valve for this purpose.
The “Hi” knob of the manifold
valve must always be kept closed.

CAUTION

CAUTION

Before using the vacuum pump
adapter, read the vacuum pump
adapter manual, and use the
adapter correctly.

In order to prevent charging errors with
A/C that uses R410A, the screw diameter
at the service valve charging port has
been changed. When recharging or per-
forming other servicing, use the special
charging hose and manifold gauge.

When using a hex wrench to open the spindle, an

extremely small amount of refrigerant may leak. 

This does not indicate a problem.

Use a hex wrench of a type to which force can be

easily applied. 

Содержание GRF194MR5IAA

Страница 1: ...Required for Installation 2 INSTALLA TION SITE SELECTION 3 2 1 Indoor Unit 2 2 Outdoor Unit 2 3 Outer Dimensions of Outdoor Unit 2 4 Diagram of Outdoor Unit Installation 3 INSTALLATION PROCESS 8 3 1 E...

Страница 2: ...king up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut yo...

Страница 3: ...utlet or A C workshop 1 4 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrige...

Страница 4: ...stricted air flow around the unit install the unit within the maximum elevation difference H1 H2 H3 above or below the outdoor unit and within a total tubing length L1 L2 L1 L2 L3 from the outdoor uni...

Страница 5: ...n 17 m 6 35 6 35 9 52 Union 12 7 9 52 9 52 A B 94 124 types Outdoor unit Indoor unit 184 type Flare 9 52 Union 12 7 12 7 Flare 9 52 A joint for connecting tubes of different sizes More than 17 m Fig 2...

Страница 6: ...52 C 94 124 types Outdoor unit Indoor unit 94 124 types 184 type Less than 17 m 6 35 6 35 9 52 9 52 9 52 6 35 9 52 A 9 52 B 9 52 C 94 124 type Outdoor unit Indoor unit 94 124 type 94 124 type GRF244MR...

Страница 7: ...will not magnify operating noise or vibration Fasten in place with the anchor bolts M10 provide a base using concrete or similar material and ensure proper drainage select a location where there is n...

Страница 8: ...ure below are spaces that are required in order to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In pr...

Страница 9: ...own and pull it toward you Refer to 2 4 Diagram of Outdoor Unit Installation 3 Remove the tubing panel in order to attach covers as needed according to the number of indoor units Refer to 2 4 Diagram...

Страница 10: ...ngth 3 5 Caution before Connecting Tubes Tightly a Be sure to apply a sealing cap or water proof tape to prevent dust or water from getting into the tubes before they are used b Be sure to apply refri...

Страница 11: ...1 clamp approx every 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the condensation drain hose splits away from the bundle and drip...

Страница 12: ...is cycle is repeated until the room temperature is lowered to the target level During the heating cycle the direction of refrigerant flow is reversed by a 4 way valve As a result the condenser draws h...

Страница 13: ...th pressure gauges to the service port on the Hi Lo B A C Service valve on narrow tube side Service valve on wide tube side With push pin Hex wrench nominal size 4 mm not provided Manifold gauge speci...

Страница 14: ...in 6 With a hex wrench turn the valve stem on the nar row tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again 7 With a standar...

Страница 15: ...le at the outdoor unit This work must be performed during cooling operation The refrigerant gas cannot be recovered during heating operation During winter or if the temperature sensor prevents cooling...

Страница 16: ...nstructions 5 1 General Precautions on Wiring 1 Before wiring confirm the rated voltage of the unit as shown on its nameplate then carry out the wiring closely following the wiring diagram 2 Provide a...

Страница 17: ...ly Single phase AC 220 240 V B CAUTION Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit 5 3 Wiring Syst...

Страница 18: ...ature sensor Humidity sensor BK BK Black W White R Red GRN Green Y Yellow BL Blue GY Gray Fig 27a INDOOR UNIT BK BK Control panel Terminal board Display receiver panel GRN Fan motor Flap motor W W W W...

Страница 19: ...7 9 CN35 WHT 3 1 5 SI BRN TERMINAL BASE 3P 6 6 7 7 WHT BLK WHT PAM PAM CN23 4 4 5 5 WHT BLK WHT 1 1 2 2 BLK BLK WHT CT CT WHT CN08 1 1 3 3 BLK BLK WHT PRY PRY RED CN21 W W AC200 L2 CN29 BLK YEL YEL BL...

Страница 20: ...PCB HS ORG 7 9 CN35 WHT 3 1 5 SI BRN TERMINAL BASE 3P 6 6 7 7 WHT BLK WHT PAM PAM CN23 4 4 5 5 WHT BLK WHT 1 1 2 2 BLK BLK WHT CT CT WHT CN08 1 1 3 3 BLK BLK WHT PRY PRY RED CN21 W W AC200 L2 CN29 BLK...

Страница 21: ...it on the termi nal plate and fix it securely with the removed ter minal screw using a screwdriver For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the...

Страница 22: ...iring Instructions for the Outdoor Unit The below explanation uses model GRF244MR5IAA as an example With model GRF194MR5IAA there is no terminal block C Be sure to correctly align inter unit cables A...

Страница 23: ...h unit If there is cold air mixed in with the warm air check the tubing connections again Checking tubing and wiring Perform the test run and check that operation is nor mal If there is an error in tu...

Страница 24: ...tubing connections Drain connections are secure and water drains properly Putty has been used to close the hole in the wall All service valves are fully open Remote controller signals are being posit...

Отзывы: