– 5 –
1. SPECIFICATIONS
1-1 Unit Specifications
MODEL No. Indoor Unit SPA360X5TAA
Outdoor Unit GR360X7TAA
POWER SOURCE
380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE
Cooling
Capacity
kW
10.6
BTU / h
36,000
Air circulation (Hi/Me/Lo)
m3 / h
1,680/1,410/1,200
Moisture removal(High)
Liters/h
4.8
ELECTRICAL RATINGS
Voltage rating
V
380
400
415
Available voltage range
V
342 - 456
Running amperes*
A
5.2
5.2
5.2
Max. running amperes**
A
6.7
6.5
6.4
Power input
kW
3.07
3.11
3.15
Power factor
%
89.7
86.3
84.3
C.O.P
W / W
3.45
3.35
3.37
Max. starting amperes
A
31
33
34
FEATURES
Controls
Microprocessor
Timer
ON / OFF 12-hours
ON/OFF 24-hours & Program
Fan speed (Indoor)
3 and Automatic control
Airflow direction (Indoor)
Automatic (Remote control)
Air filter
Washable, easy access
Remote controller (Accessory) RCS-5PN3E
Refrigerant control
Capillary tube
Drain pump (drain connection)
No (20A, OD26mm)
Compressor
Rotary
Operation sound
Indoor - Hi/Me/Lo dB - A
47 / 43 / 39
Outdoor - Hi
dB - A
54
REFRIGERANT TUBING
Limit of tubing length
m (ft.)
50 (164)
Limit of tubing length at shipment
m (ft.)
15 (49)
Limit of elevation difference
m (ft.)
Outdoor unit is higher than indoor unit: 50 (164)
between the two units
Outdoor unit is lower than indoor unit: 30 (98)
Refrigerant tube
Narrow tube
mm (in)
9.52 ( 3 / 8 )
outer diameter
Wide tube
mm (in)
19.05 ( 3 / 4 )
Refrigerant amount at shipment
kg
R22 - 4.0
DIMENSIONS & WEIGHT
Indoor unit
Outdoor unit
Unit dimensions
Height
mm (in) 250 (9-27/32)
1,235 (48-20/32)
Width
mm (in) 1,570 (61-26/32)
940 (37)
Depth
mm (in) 670 (26-12/32)
340 (13-12/32)
Package dimensions
Height
mm (in) 336 (13-7/32)
1,326 (52-7/32)
Width
mm (in) 1,670 (65-24/32)
1,016 (40)
Depth
mm (in) 782 (30-25/32)
416 (16-12/32)
Net weight
kg (lb)
41 (90)
94 (207)
Shipping weight
kg (lb)
51 (112)
101 (223)
Shipping volume
m
3
(Cu. ft.)
0.439 (15.5)
0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions(*) :
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB