– 30 –
3. ELECTRICAL DATA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
220 - 240 V / 1 phase / 50 Hz
Rating conditions
A
0.43 / 0.43
0.75 / 0.78
13.32 / 13.74
14.50 / 14.95
kW
0.09 / 0.10
0.17 / 0.19
2.71 / 2.82
2.97 / 3.11
Full load conditions
A
0.43 / 0.43
0.75 / 0.78
18.87 / 18.03
20.05 / 19.24
kW
0.09 / 0.10
0.17 / 0.19
3.92 / 3.93
4.18 / 4.22
Starting amperes
A
1 / 1
1 / 1
67 / 73
69 / 75
Rating Conditions
: Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature
35
°
C DB
Full Load Conditions : Indoor Air Temperature
35
°
C DB / 22.5
°
C WB
Outdoor Air Temperature
52
°
C DB
Indoor model : SPA250X5TAA
Outdoor model : GR250X5TAA
Indoor model : SPA250X5TAA
Outdoor model : GR250X7TAA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.43 / 0.43
0.75 / 0.78
4.32 / 4.20
4.69 / 4.56
kW
0.09 / 0.10
0.17 / 0.19
2.46 / 2.47
2.72 / 2.76
Full load conditions
A
0.43 / 0.43
0.75 / 0.78
5.52 / 5.22
5.90 / 5.60
kW
0.09 / 0.10
0.17 / 0.19
3.27 / 3.26
3.52 / 3.54
Starting amperes
A
1 / 1
1 / 1
25 / 28
26 / 30
Indoor model : SPA360X5TAA
Outdoor model : GR360X7TAA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.95 / 0.98
1.51 / 1.56
4.46 / 4.37
5.23 / 5.15
kW
0.20 / 0.22
0.33 / 0.37
2.54 / 2.56
3.07 / 3.15
Full load conditions
A
0.95 / 0.98
1.51 / 1.56
5.96 / 5.64
6.74 / 6.44
kW
0.20 / 0.22
0.33 / 0.37
3.53 / 3.51
4.06 / 4.10
Starting amperes
A
2 / 2
3 / 3
27 / 30
31 / 34
3-1 Electrical characteristics