SUMMARY TABLE OF ALARMS

= Auto
= Manual

7.8 - SPECIAL OPERATING FEATURES

• Water circulating pump control:

- the pump is actuated when the unit operating,
- the pump is stopped when the unit is stopped. The shut-down of the pump is delayed 1 minute after the compressor stops,
- the unit's electronic control features a frost protection device that automatically starts the water circulating pump

depending on the outside temperature (threshold: 0

°

C), even if the unit is turned off.

In the event of a faulty outside temperature sensor, circulating pump operation is forced, for safety reasons.
The "Water output" alarm (E41) stops the circulating pump when this alarm shifts to manual reset. In the event of a fault,
the alarm report is actuated.

Alarm

Code Inhibition delay

R e s e t

Remarks

A

B

A

B

Water inlet 
temperature 
probe fault, Ai1

E 4 0

X

X

X

X

A

Water inlet 
temperature 
probe fault, Ai2

E 0 6

X

X

X

X

A

Outside 
temperature 
sensor fault, Ai4

E 4 2

X

X

X

X

A

Force water pump 
operation

H.P. circuit A

E 0 1

X

X

A / M

H.P. circuit B

E 2 1

X

X

A / M

L.P. circuit A

E 0 2

120'' at start-up

X

X

A / M

L.P. circuit B

E 2 2

120'' at start-up

X

X

A / M

Thermic, 
compressor, 
circuit A

E 0 3

X

X

M

Thermic, 
compressor, 
circuit B

E 2 3

X

X

M

Thermic, fan,   
circuit A

E 0 4

X

X

M

Thermic, fan,  
circuit B

E 2 4

X

X

M

From probe Ai2

A / M

(water outlet)
Threshold  = 6

°

 C

Configuration 
error

E 4 5

X

X

X

X

X

Consult the After-Sales 
Service Department

A

Shutdown by 
remote contact

E 0 0

X

X

X

X

X

A

No alarm report with 
H72 = 1

Threshold = 35 

°

C

Water inlet 
temperature too 
high

E 4 6

2 '

X

A / M

30'' at start-up

If manual reset

X

X

Water flow rate

E 4 1

10'' in operation

E 0 5

X

X

Compressor 

s t o p

Fan stop

Water 

pump 

shutdown

See also reset of the 
corresponding circuit 
breaker

Anti-freeze 
(water heat 
exchanger)

Содержание CMHGV 2101

Страница 1: ...1 July 2006 10 11 369 GB 05 INSTALLATION INSTRUCTIONS AIR COOLED WATER CHILLER WITH BUILT IN HYDRAULIC MODULE AIR WATER R 407 C refrigerant CMHGV 2101 2140...

Страница 2: ...total weight 4 In the case of a new charge do not use the charging cylinder use a balance and a dip pipe type R 407 C cylinder charge the weight of R 407 C as per the value indicated on the unit s ide...

Страница 3: ...ransport refrigerating circuit electrical cabinet cassis and cabinet The unit must not be installed near the following sources of heat combustible materials return air intake of an adjacent building T...

Страница 4: ...ad losses 4 2 ELECTRICAL CONNECTION 4 2 1 GENERALITIES In all cases refer to the wiring diagrams supplied with the unit or supplied upon request The acceptable voltage variation is 10 during operation...

Страница 5: ...erisation See 7 The lengths indicated below correspond to a voltage drop less than 5 in the cable CMHGV Starting current A Max total current A Power supply cable section mm2 Max connection length m 21...

Страница 6: ...lack wires supplied as shown opposite 5 2 5 800 W ANTI FREEZE RESISTANCE Code 70200010 Power supply and control of this resistance shall be separate from all other installation circuits It must be ins...

Страница 7: ...CKS TO BE MADE Check that the rotation direction of the fan s and the pump is correct If not reverse 2 phases on the electrical power supply HP and LP pressure and amperages are in accordance with the...

Страница 8: ...ATION 7 3 1 DISPLAY KEYBOARD 1 Key for local On Off control access to parameters in combination with button 2 alarm clearance hour counter reset 2 Key for access to parameters in combination with butt...

Страница 9: ...d triggering of cooling circuits depending on the difference in relation to the water setpoint temperature Note An automatic refrigerating circuit switchover system allows their operating time to be s...

Страница 10: ...se or decrease a parameter value 7 6 2 PARAMETERS ACCES DIAGRAM Accessible to qualified personnel only after entering the password PSS Note 1 Indicator lamps 6 and 8 flash when levels 1 and above are...

Страница 11: ...ly press buttons 1 and 2 The message appears Display the password 199 using buttons 1 and 2 and validate it by simultaneously pressing buttons 1 and 2 It is now possible to enter the parameters sectio...

Страница 12: ...B A B Water inlet temperature probe fault Ai1 E 4 0 X X X X A Water inlet temperature probe fault Ai2 E 0 6 X X X X A Outside temperature sensor fault Ai4 E 4 2 X X X X A Force water pump operation H...

Страница 13: ...ing hysteresis in the compressor section CP the difference between the 2 stages is factory set at 1 5 k Modification is possible To do this modify parameter C05 in the compressor section CP Dynamic se...

Страница 14: ...ay lead to serious burns 9 1 PERIODIC CHECKS Carry out the following operations at least once a year the frequency depends on the installation and operating conditions Cleaning the air exchanger Check...

Страница 15: ...the application limits defined in the documentation shall result in the cancellation of PED CE marking compliance which shall fall under the liability of the individual who carried out these modificat...

Страница 16: ...H60 Probe Ai4 offset 12 70 12 70 C F 0 H64 Temperature measurement unit C F 0 1 flag 0 H65 Family series address for communication 0 14 num 0 H66 Device series address for communication 0 14 num 1 H7...

Страница 17: ...5 C 4 6 8 10 12 14 16 18 20 3 4 5 6 7 25 C 45 C 35 C 15 C HIGH PRESSURE LOW PRESSURE High pressure bar Water outlet temperature C CMHGV 2101 Low pressure bar Water outlet temperature C High pressure b...

Страница 18: ...licy of continuous development our products are liable to modification without notice R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France Tel 33 4 74 00 92 92 Fax 33 4 74 00 42 00 R C S Bourg en Bresse...

Отзывы: