12
SUMMARY TABLE OF ALARMS
A = Auto
M = Manual
7.8 - SPECIAL OPERATING FEATURES
• Water circulating pump control:
- the pump is actuated when the unit operating,
- the pump is stopped when the unit is stopped. The shut-down of the pump is delayed 1 minute after the compressor stops,
- the unit's electronic control features a frost protection device that automatically starts the water circulating pump
depending on the outside temperature (threshold: 0
°
C), even if the unit is turned off.
In the event of a faulty outside temperature sensor, circulating pump operation is forced, for safety reasons.
The "Water output" alarm (E41) stops the circulating pump when this alarm shifts to manual reset. In the event of a fault,
the alarm report is actuated.
Alarm
Code Inhibition delay
R e s e t
Remarks
A
B
A
B
Water inlet
temperature
probe fault, Ai1
E 4 0
X
X
X
X
A
Water inlet
temperature
probe fault, Ai2
E 0 6
X
X
X
X
A
Outside
temperature
sensor fault, Ai4
E 4 2
X
X
X
X
A
Force water pump
operation
H.P. circuit A
E 0 1
X
X
A / M
H.P. circuit B
E 2 1
X
X
A / M
L.P. circuit A
E 0 2
120'' at start-up
X
X
A / M
L.P. circuit B
E 2 2
120'' at start-up
X
X
A / M
Thermic,
compressor,
circuit A
E 0 3
X
X
M
Thermic,
compressor,
circuit B
E 2 3
X
X
M
Thermic, fan,
circuit A
E 0 4
X
X
M
Thermic, fan,
circuit B
E 2 4
X
X
M
From probe Ai2
A / M
(water outlet)
Threshold = 6
°
C
Configuration
error
E 4 5
X
X
X
X
X
Consult the After-Sales
Service Department
A
Shutdown by
remote contact
E 0 0
X
X
X
X
X
A
No alarm report with
H72 = 1
Threshold = 35
°
C
Water inlet
temperature too
high
E 4 6
2 '
X
A / M
30'' at start-up
If manual reset
X
X
Water flow rate
E 4 1
10'' in operation
E 0 5
X
X
Compressor
s t o p
Fan stop
Water
pump
shutdown
See also reset of the
corresponding circuit
breaker
Anti-freeze
(water heat
exchanger)