background image

4

-2. Dry Operation (Dehumidification)

Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to

dehumidify without greatly reducing the room temperature. The air conditioner repeats the

 ON/OFF

 cycle 

automatically as shown in the chart below according to the room temperature.

Intermittent ventilation occurs by switching the indoor fan speed between L 

LL.

Dry operation does not occur when the room temperature is under 15°C, which is the monitor zone.

When the compressor stops, the indoor fan stops as well.

NOTE

Room temp.

Cooling operation

T+2

°

C

Set temp. T

°

C

T–1

°

C

Monitor zone

Both the indoor and outdoor units stop.

Room temp. 15 

°

C

*Dry A zone

Compressor :

FMI (indoor fan) :

Continuous operation

L (low speed) / LL (very low speed) intermittent ventilation 
only while the compressor is ON.

*Dry B zone

Compressor :

FMI (indoor fan) :

Intermittent operation (ON for 3 minutes and OFF for 9 minutes)

L (low speed) / LL (very low speed) intermittent ventilation 
only while the compressor is ON.

4

-

3

. Freeze Prevention (Cooling)

This function prevents freezing of the indoor heat exchange coil.

When the compressor has been running for 10 minutes or more and the temperature of the indoor heat

exchange coil falls below –1°C, the control circuit stops the compressor for at least 6 minutes. The compressor

does not start again until the temperature rises above 8°C or 6 minutes has elapsed.

ON

ON

ON

ON

OFF

OFF

Set speed

More than

10 minutes

6 minutes

T+1

°

C

Indoor heat exch. 
coil temp.

–1

°

C

Compressor

Indoor fan

Room temp.

Thermo. OFF

Thermo. ON

Set temp. T 

°

C

More than

10 minutes

More than

6 minutes

Set speed

13

Содержание 387106947

Страница 1: ...TECHNICAL DATA SERVICE MANUAL INDOOR UNIT DSAV182C5TAA DSAV222C5TAA SPLIT SYSTEM AIR CONDITIONER 0 8180 312 0 04 2004 Model No Product Code No DSAV182C5TAA 387106947 DSAV222C5TAA 387106948...

Страница 2: ...w wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line...

Страница 3: ...3 4 4 Drain Pump and Float Switch 14 5 TROUBLESHOOTING 15 5 1 Check before and after troubleshooting 15 5 2 Air conditioner does not operate 15 5 3 Some part of air conditioner does not operate 19 5 4...

Страница 4: ...ions Unit Height mm Width mm Depth mm Package dimensions Unit Height mm Width mm Depth mm Volume m3 Weight Unit Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power level measured at operati...

Страница 5: ...dth mm Depth mm Package dimensions Unit Height mm Width mm Depth mm Volume m3 Weight Unit Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power level measured at operating conditions HIGH spe...

Страница 6: ...36 GRY VLT 18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE Fan speeds H...

Страница 7: ...RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE Fan speeds H M L measured at o...

Страница 8: ...TH1 Resistance Thermistor Room sensor TH2 Resistance Drain pump Model Rating Voltage Input Total head capacity Safety float switch Model Contact rating ATR J105 AC 230V 50 60Hz 19V 0 526A 10 VA Prima...

Страница 9: ...9...

Страница 10: ...2 DIMENSIONAL DATA 10...

Страница 11: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagrams 11...

Страница 12: ...ant pressure the control circuit has a built in automatic time delay to allow the internal pressure to equalize As a protective measure the control circuit switches the compressor OFF not before than...

Страница 13: ...ndoor fan Continuous operation L low speed LL very low speed intermittent ventilation only while the compressor is ON Dry B zone Compressor FMI indoor fan Intermittent operation ON for 3 minutes and O...

Страница 14: ...Drain Pump Float Switch NOTE Either in Heating or another mode or the unit is stopped when the float switch is turned ON the drain pump operates for 20 minutes minimum OFF OFF OFF OFF OFF OFF ON ON O...

Страница 15: ...is not damaged Check that lead wires and connectors are firmly connected Check that wiring is correct 5 2 Air conditioner does not operate 5 2 1 Circuit breaker trips or fuse blows A When the circuit...

Страница 16: ...t in ON position Set OPERATION selector switch to ON Indoor PCB Ass y is defective NO Check power supply Power is being supplied to the indoor unit Circuit breaker is tripped Power failure Reset break...

Страница 17: ...sure resistance of primary and secondary winding of transformer TR Indoor PCB Ass y is defective OK Measure resistance of indoor and outdoor fan motor winding FM Measure resistance of compressor motor...

Страница 18: ...Ass y is defective Indoor PCB Ass y is defective Check voltage between terminals No 2 and No 4 at terminal plate 220 AC No voltage appears OK NO Is room temperature too low Try to lower setting tempe...

Страница 19: ...tter in bearings Remove foreign matter or repair Repair or replace Measure resistance of outdoor fan motor winding Check fan motor capacitor Measure resistance of flap motor winding Fan cannot be turn...

Страница 20: ...otor winding is abnormally high Refrigerant gas shortage Charge refrigerant gas Measure power supply voltage Rotor may be locked up The voltage is too low 5 3 4 Compressor and outdoor fan do not run F...

Страница 21: ...ion of remote control unit Cool air from air conditioner reaches position directly Change position of remote control unit Wide and narrow tubes between indoor unit and outdoor unit are insulated Insul...

Страница 22: ...will blink when either indoor coil thermistor or room air thermistor is defective At the same time the outdoor unit will stop Indoor unit will operate only for ventilation NOTE Operation lamp on fron...

Страница 23: ...sure the resistance by placing a probe on each terminal screw on the terminal plate Fig 2 Note that the ground line terminal should be skipped for the check 6 1 4 Measurement of Insulation Resistance...

Страница 24: ...n place a probe on the capacitor terminals as shown in Fig 7 Observe the deflection of the pointer setting the resistance measuring range of the multimeter to the maximum value The capacitor is good i...

Страница 25: ...s on the PCB of each indoor unit with the switch positions of its remote control unit To change address on PCB 1 Set the switch n 2 to off position on the address dip switch S01 see detail on figure T...

Страница 26: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France T l 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728...

Отзывы: