2
- 4
2-WAY MULTISET VRF SYSTEM
Remote Controller Functions
2
0000
Not displayed
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
Filter sign ON time
(filter lifetime)
0005
Use the filter clogging sensor.
0000
Standard (setting at time of shipping)
Degree of filter fouling
0001
Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
Central control address
0099
No central control address set (setting at time of shipping)
0000
Normal (setting at time of shipping)
Operating mode
priority change
0001
Priority
Compressor ON
Compressor OFF
0000
MED 1 min., LO 3 min.
LO
0001
MED
LO
0002
LO
LO
0004
MED 1 min., LO 3 min.
MED
0005
MED
MED
Fan speed when
heating thermostat is
OFF
0006
LO
MED
0000
No shift
0001
Shifts intake temperature 1 C down.
0002
Shifts intake temperature 2 C down.
0003
Shifts intake temperature 3 C down.
0004
Shifts intake temperature 4 C down.
0005
Shifts intake temperature 5 C down.
Heating intake
temperature shift
0006
Shifts intake temperature 6 C down.
0000
No heater
Electric heater
installation
0001
Heater installed
0000
No (setting at time of shipping)
Hu
Change to remote
controller sensor
thermostat differential
Mode
dependency
midifying when
heater thermostat is
OFF
0001
Yes
0000
Thermostat OFF differential: – 1.0 deg (setting at time of shipping)
Thermostat OFF differential: – 0.5 deg
0001
0000
Normal
0001
0000
Normal
Cooling-only
0001
Cooling only
List of Simple Setting Items
2. Simple Settings Function