Dimentions of connections (shows the inner diameter of tubing)
Unit: mm
Position
A
B
C
D
E
F
G
Size
ø
28.58
ø
25.4
ø 19.05
ø
15.88
ø
12.7
ø
9.52
ø
6.35
7-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely
following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each
unit, and a power supply disconnect and circuit breaker
for overcurrent protection should be provided in the
exclusive line.
(3) To prevent possible hazards due to insulation failure, the
unit must be grounded.
(4) Each wiring connection must be done in accordance with
the wiring system diagram. Wrong wiring may cause the
unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorised changes in the internal wiring can be very
dangerous. The manufacturer will accept no responsibility
for any damage or misoperation that occurs as a result of
such Unauthorised changes.
(7) Regulations on wire diameters differ from locality to locality.
For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must insure that installation complies with all relevant
rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as follows:
●
The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
●
Use shielded wires for inter-unit control wiring between
units and ground the shielded on both sides.
(9) If the power supply cord of this appliance is damaged, it must
be replaced by a repair shop appointed by the manufacture,
because special purpose tools are required.
7-2. Recommended Wire Length and Wire Diameter for Power Supply System
AWG: American Wire Gauge
Outdoor Unit
(A) Power Supply
Time Delay Fuse
4 mm
2
or Circuit Capacity
Capacity
Max. Wire Diameter
GRV250L7/R7
110 m
15 A
25 A
5.5 mm
2
(AWG#10)
GRV360L7/R7
75 m
20 A
25 A
5.5 mm
2
(AWG#10)
GRV480L7/R7
61 m
20 A
25 A
5.5 mm
2
(AWG#10)
GRV250L5/R5
20 m
35 A
50 A
14 mm
2
(AWG#10)
Type
Terminal Base
Indoor Unit
(A) Power Supply
Time Delay Fuse
2.5 mm
2
or Circuit Capacity
Capacity
Max. Wire Diameter
245 m
15 A
50 A
14 mm
2
(AWG#6)
Terminal Base
7. ELECTRICAL WIRING (Only for PACKAGE Outdoor Units)
Wide tube
Narrow tube
Max. diameter
Min. diameter
Insulation
Insulation
Max. diameter
Min. diameter
Narrow tube
Wide tube