When the operation selector on the grille assy is moved from the ON or TEST position to the OFF (Self-diagnostics)
position, the indicator lamps will flash (or remain ON) for 5 seconds and then turn OFF for 2 seconds (buzzer sounds
once) to indicate the presence of a sensor failure or the activation of a protective function. Self-diagnostics is completed
when the buzzer sounds 3 beeps. If there is no trouble, the lamps do not flash. Also note that the corresponding parts
listed below may not be present in some models.

Other

 : 

Timer lamp flashes (3-second intervals): I/D float switch activated.

NOTE

 : 

If the operation lamp continues to flash (orange) even when the operation switch has been moved to
the OFF position, an indoor unit external ROM failure has occurred. (E14) After inspection or repair
is completed, be sure to move the operation switch (on the electrical box) to the DEMO position,
turn the power OFF and ON and erase the diagnostics contents.

Control 1

Control 2

Initial self-

Short-circuit terminals 2 and 4 on

Short-circuit terminals 2 and 3 on

Probable location of malfunction

diagnostics

the indoor unit terminal plate

the outdoor unit terminal plate

No change

-

Indoor unit circuit board failure

Only operation lamp

Change: Operation lamp and Service

Change: Operation lamp and Service

Outdoor unit circuit board failure

illuminates

lamp illuminate, and Timer lamp flashes

lamp illuminate, and Timer lamp flashes

Change: Operation lamp and Service

Change: only operation lamp illuminates

Failure (open circuit, contact failure,

lamp illuminate, and Timer lamp flashes

etc.) in the inter-unit cable

- Turn the power OFF before performing short circuiting work. 
- During the self-diagnostics check, the check results are the first indication when the operation switch is moved to OFF
  while the indicators are flashing after power ON 

DEMO (5 seconds) 

ON. 

- Before performing the above checks, perform DEMO operation, and check that AC 220 V is output toterminals 1 and
  2. If it is not output, there is a failure related to the indoor unit power.

Details of Self-Diagnostics

*

*

18

Содержание 387106972

Страница 1: ...TECHNICAL DATA SERVICE MANUAL INDOOR UNIT DSAF94MR5IA DSAF124MR5IA SPLIT SYSTEM AIR CONDITIONER 0 8180 394 1 09 2006 387106973 DSAF124MR5IA Model No Product Code No DSAF94MR5IA 387106972...

Страница 2: ...w wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line...

Страница 3: ...DATA 10 3 ELECTRICAL DATA 11 3 1 Electric Wiring Diagrams 11 4 FUNCTION 12 4 1 Operation Functions 12 4 2 Protective Functions 14 4 3 Drain Pump and Float Switch 15 5 TROUBLESHOOTING 16 6 CHECKING EL...

Страница 4: ...ions Unit Height mm Width mm Depth mm Package dimensions Unit Height mm Width mm Depth mm Volume m3 Weight Unit Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power level measured at operati...

Страница 5: ...Width mm Depth mm Package dimensions Unit Height mm Width mm Depth mm Volume m3 Weight Unit Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power level measured at operating conditions HIGH s...

Страница 6: ...K GRY 15 GRY VLT 15 WLT RED 30 RED YEL 101 Safety devices Type Operating temp Open C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE Fan sp...

Страница 7: ...15 WLT RED 30 RED YEL 101 Safety devices Type Operating temp Open C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE Fan speeds H M L measur...

Страница 8: ...AC 230 V 50 60 Hz 13 7 V 0 4 A 5 48 VA Primary WHT WHT 307 10 Secondary BRN BRN 1 8 10 150 C DTN C583G3U TKS121B 0 C 188 0 4 DTN C502H3T TKS128B 25 C 5 0 3 C7 M3 SY 25 C 60 RH 5 RH 31 0 BI 1300 2725 2...

Страница 9: ...the disconnected fan motor sockets in step 2 as shown in the Figure 5 Place the cable neatly in the box and reinstall the cover plate NOTE HH Using the booster cable H At shipment How to read the diag...

Страница 10: ...2 DIMENSIONAL DATA Units mm 10...

Страница 11: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagrams 11...

Страница 12: ...t low operation speeds and PAM control at high operation speeds making the most effective use of power The compressor operation frequency varies depending on the relative humidity The indoor fan opera...

Страница 13: ...temperature either 60 minutes prior or 30 minutes prior to the set ON timer time and operation is started in advance of the set ON time The indoor fan speed is Medium COOL Indoor temperature Set temp...

Страница 14: ...tops Once the freeze condition is detected the air conditioner will work less than the maximum frequency until it is turned off Approx 53 Normal operation At start of operation A High LL Stopped A B C...

Страница 15: ...4 3 Drain Pump and Float Switch...

Страница 16: ......

Страница 17: ...ion switch Ordinarily be sure this is always set to NORMAL The DEMO position is used for inspections and similar maintenance 1 Turn the power switch ON 2 Move the operation selector on the remote cont...

Страница 18: ...ostics contents Control 1 Control 2 Initial self Short circuit terminals 2 and 4 on Short circuit terminals 2 and 3 on Probable location of malfunction diagnostics the indoor unit terminal plate the o...

Страница 19: ...MO and start operation using the remote controller If there are no problems with the above then check the outdoor unit 1 The rated voltage must be present between inter unit cables 1 and 2 Connect a 5...

Страница 20: ...tance from the noise source 1 Use shielded wires 2 Move unit away from the noise source Trouble Either of the following trouble may occur 1 The unit may stop suddenly during operation 2 Indicator lamp...

Страница 21: ...sure the resistance by placing a probe on each terminal screw on the terminal plate Fig 2 Note that the ground line terminal should be skipped for the check 6 1 4 Measurement of Insulation Resistance...

Страница 22: ...n place a probe on the capacitor terminals as shown in Fig 7 Observe the deflection of the pointer setting the resistance measuring range of the multimeter to the maximum value The capacitor is good i...

Страница 23: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France T l 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728...

Отзывы: