Tc
7000 BTU/h
9000 BTU/h
12000 BTU/h
32°C
33°C
34°C
5-7. Cold Draft Prevention (Heating)
●
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat
exchange coil have sufficiently warmed up.
●
STANDBY lamp on front of the indoor unit lights up when this function is working.
●
Indoor fan operates in LL until indoor heat exchange coil temperature reaches 32°C.
●
In case of after releasing the defrosting, indoor fan halt its operation until the coil temperature reach 32°C.
●
When the coil temperature rises above Tc°C, indoor fan operates in set speed.
The operation temperature shown as Tc in the chart differs by models.
NOTE
OFF
ON
OFF or
Set speed
Indoor fan
Standby lamp
Indoor heat exch.
coil temp. (
°
C)
Tc
Max. 10minutes
LL
Release of
cold draft prevention
24