30
Aug/2017 - V1
Technetix Group Limited
Product User Manual
AIMA3000.ASMM
7.2.1 ASMM Module
Click on the
ASMM
in the left column of the Modules page.
On this page, you can view Module Information, Confi guration and Alarm Settings panels.
Click on the
Refresh
button to update module information, for example after a new module is inserted.
In the confi guration panel, you can toggle Alarm Control. Choose the setting you want then click on the
Submit
button.
Table 7-1 ASMM Common parameters
(not confi gurable)
Parameter
Units
HIHI
HI
Normal
LO
LOLO
DeadBand
Threshold
changeable
by user
Default alarm
enable
Temperature
°C
63
58
-
3
-2
2
N
ON
+5V Input Voltage
Vdc
5.6
-
5
-
4.4
0.2
N
ON
Note:
Alarm Control is enabled by default.
In the Alarm Settings panel, you can view alarm parameter names and the associated settings.
7.2.2 Other Modules
Module Information, Confi guration, and Alarm Settings information for other module types can be found in the associated
module's manual.