 ST – 450 z PID

operation in the sustain cycle.

Boiler hysteresis

This option is used to set the hysteresis of the preset temperature. It is a 
difference between the sustain

 

cycle activation temperature and the 

temperature to return to operation

 

cycle (e.g. if the preset temperature is 60°C 

with hysteresis equal to 3°C, switching to sustain

 

mode is performed after the 

temperature of 60°C is reached, and the device returns to operation cycle once 
the temperature drops to 57°C).

Once the  controller operation without PID  is selected the following  functions 
(assigned to PID only) will disappear from the main and installation menus:
firing,
damping
boiler power,
air correction,
fuel type,
supervision mode.

III.20.  Room controller

This function is used to define the type of the controller connected to ST-450 controller with PID and 
programme the room controller operation:

a)

Off  – 

no

 

room controller connected

b)

Standard controller –

 two-state room controller

c)

TECH controller –

 controller with RS communication function.

d)

Room controller unit

Off

 – state of the room controller has no impact on other settings

Boiler

 – once the room controller indicates that the preset temperature has 

been reached the temperature preset on the boiler will be reduced (detailed 
settings see Item II.15) 

Central heating pump 

- once the room controller indicates that the preset 

temperature   has   been   reached   the   central   heating   pump   will   be   turned   off 
(detailed settings see Item II.15)

After 

TECH Controller 

or

 standard 

option is enabled a letter 

"P"

 appears in 

the upper part of the display in the main screen of the controller. A flashing 
letter "P" indicates that the temperature in the room is too low. As soon as the 
required room temperature is reached the letter "P" stops flashing and stays on.
e)     

Information  about  the  programme  –  

This  function  allows  the  user  to 

check the programme version of the TECH room controller connected.

   

III.21 Display contrast

Allows changing the display contrast settings.

IV. Service Menu

 

To access the servicing functions of the 

ST-450

 controller you must enter 

- 24 -

Содержание ST-450zPID

Страница 1: ......

Страница 2: ...22 Wieprz is compliant with the Regulation by the Ministry of Economy Journal of Laws Dz U 155 Item 1089 of July 21 2007 implementing provisions of the Low Voltage Directive LVD 2006 95 EC of January...

Страница 3: ...cted from the mains before working on the power supply cable connections device installation etc All connection works must only be carried out by qualified electricians Before activating the controlle...

Страница 4: ......

Страница 5: ...In this type of controller the blow in power is calculated on the basis of the measurement of the temperature of the boiler and the temperature of flue gas measured on the outlet of the boiler Operati...

Страница 6: ...not drop below that level for a period of 30 seconds factory set firing time Operation After completion of firing cycle the controller enters the operation cycle and a message reading PID OPERATION a...

Страница 7: ...e generator brings the user to the first level menu The first three menu options are shown on the display Turn the knob to move to subsequent options Press the knob to select a given function Similar...

Страница 8: ...temperature within the range of 45 C to 80 C The preset central heating system temperature can also be changed directly in the main screen of the controller by turning the pulser knob Additionally the...

Страница 9: ...n manual operation is additionally available II 7 Operation mode In this function the user selects one of four options of the boiler s operation House heating When you select this option the controlle...

Страница 10: ...g h When this is so one of the pumps will switch on earlier than the other one but after both thresholds are crossed both pumps will run together The central heating pump will run all the time while...

Страница 11: ...nd Saturday and Sunday separately Set mode 2 Monday Friday Saturday Sunday Similarly to the previous mode it is necessary to select specific times and required deviations from the temperature preset f...

Страница 12: ...om temperature reduction 15 C Minimum temperature set on the boiler 45 C factory setting Once the preset room temperature is reached indicated by the room controller the temperature preset on the boil...

Страница 13: ...ty to be fed by the feeder to the furnace III 3 TECH controller A room controller can be connected to ST 450zPID controller This function allows configuring the controller by selecting ON option Addit...

Страница 14: ...system If the sensor indicates a change in temperature deviation from set point then the solenoid will open or close partially by a preset step to restore the set point temperature 4 Opening time You...

Страница 15: ...controller menu For the valve to work properly enter set point temperatures downstream of the valve for the following four intermediate outside temperatures TEMP FOR 20 TEMP FOR 10 TEMP FOR 0 TEMP FOR...

Страница 16: ...allows you to enable protection for the boiler from excessively cold water returning from the main circuit which could cause the boiler to suffer from low temperature corrosion The return protection...

Страница 17: ...et valve temperature will drop by the value indicated here The option is unavailable if Proportional control has been selected Change of the valve presetting The setting determines the number of degre...

Страница 18: ...nt valve temperature Setting as for the main valve see Section III 4 2 4 Temperature control Setting as for the main valve see Section III 4 3 5 Opening time Setting as for the main valve see Section...

Страница 19: ...bile phone The User is notified with a text message on each alert of the boiler controller and by sending an appropriate text message at any time he or she receives a return message with the informati...

Страница 20: ...y of setting these parameters manually The method of obtaining local network parameters has been described in the instructions for the Internet module The function Reset module password may be used wh...

Страница 21: ...n Blowing can be disabled to manually control the natural chimney draught III 13 Floor pump The function is used to control the floor heating The user sets the floor heating temperature in the range b...

Страница 22: ...terval After the operation schedule has been set it is necessary to set the working and pause times for the pump while the previously selected time period is active If necessary the previous settings...

Страница 23: ...e temperature alarm is activated If the preset boiler temperature is not reached within the set time the alarm will go off The alarm is disabled by pressing the pulser knob Once the alarm is disabled...

Страница 24: ...te room controller c TECH controller controller with RS communication function d Room controller unit Off state of the room controller has no impact on other settings Boiler once the room controller i...

Страница 25: ...damage of each of the sensors the sound alarm is activated additionally signalling the defect on the relevant display e g CH sensor damaged The feeder and the blow in is disabled The pumps operate acc...

Страница 26: ...e operating mode until the temperature of 62O C is reached V 6 Control of the outlet flue gas temperature This sensor is used to continuously monitor the outlet flue gas temperature In the case of sen...

Страница 27: ...10 11 Temperature measurement range Measurement accuracy Adjustable temperature range Temperature resistance of sensors Fuse element O C O C O C O C A 0 90 1 45 80 25 90 6 3 VII Assembly NOTE Installa...

Страница 28: ...ST 450 z PID 28...

Страница 29: ...lve 13 1 Valve state 13 4 Opening time 14 5 Single step 14 6 Minimum opening 14 7 Type of valve 15 8 Weather program weekly valve program 15 9 Return protection 16 10 Room controller the option is use...

Страница 30: ...III 16 Date setting 22 III 17 Pulser sensitivity 22 III 18 Language choice 23 IV Service Menu 24 V Protections 25 V 1 Thermal protection 25 V 2 Automatic sensor control 25 V 4 Temperature protection 2...

Страница 31: ...Hence we have been entered into a register kept by the Inspection For Environmental Protection The crossed out bin symbol on a product means that the product may not be disposed of to household waste...

Страница 32: ......

Отзывы: