4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 

mains.   

The  AC  input  is  connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.   

The icon 

and 

  flashing on 

LCD display and alarm is sounding 
every second. 

The external or internal 

battery is incorrectly 
connected. 

Check  if  all  batteries  are 

connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too  high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icon 

  and

is 

flashing on LCD display and alarm 

is sounding twice every second. 

UPS is overload   

Remove  excess  loads  from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 

fed directly by the electrical 
network via the Bypass. 

Remove  excess  loads  from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove  excess  loads  from 
UPS output first. Then shut 

down  the  UPS  and  restart 
it. 

Fault code is shown as 43 and The 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 

automatically because of 
overload at the UPS output. 

Remove  excess  loads  from 

UPS output and restart it. 

Fault code is shown as 14 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 
automatically because 
short circuit occurs on the 
UPS output. 

Check  output  wiring  and  if 
connected  devices  are  in 
short circuit status. 

Fault code is shown as 01, 02, 03, 

04, 11, 12, 13, 41 and 45 on LCD 
display and alarm is continuously 
sounding. 

A  UPS  internal  fault  has 

occurred.  There  are  two 
possible results: 
1. The load is still supplied, 

but directly from AC power 
via bypass.   
2.  The  load  is  no  longer 

supplied by power.   

Contact your dealer 

        Tech Novitas FZC: P.O BOX No.: 8073, SAIF Zone, U.A.E. Phone: + 971 6 5529892 Fax:. + 971 6 5529897
Designed by Tech Novitas Corp. LLC ,Wyoming, U.S.A, www. technovitas.com  Email us at: [email protected]

Содержание venus flexi series

Страница 1: ...terruptible Power Supply System Version 1 0 User Manual Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com ...

Страница 2: ... 10 2 5 Battery kit assembly Option for Rack UPS 10 3 Operations 13 3 1 Button operation 13 3 2 LCD Panel 13 3 3 Audible Alarm 15 3 4 LCD display wordings index 15 3 5 UPS Setting 15 3 6 Operating Mode Description 18 3 7 Faults Reference Code 19 3 8 Warning indicator 19 4 Troubleshooting 20 5 Storage and Maintenance 21 6 Specifications 22 Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 ...

Страница 3: ...an be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to conne...

Страница 4: ...is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal...

Страница 5: ...e use 2 1 Rear panel view 1K India Type IEC Type NEMA Type Schuko Type Universal Type 1KL India Type IEC Type Schuko Type Universal Type 2K India Type IEC Type NEMA Type Schuko Type Universal Type Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com ...

Страница 6: ...ko Type Universal Type 3KL India Type IEC Type Schuko Type Universal Type 1KR IEC Type Universal Type Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com ...

Страница 7: ...l Type Schuko Type India Type NEMA Type 3KR IEC Type Universal Type Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com ...

Страница 8: ...ersal Type Schuko Type 2KRL IEC Type Universal Type Schuko Type Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com ...

Страница 9: ...ptacles 8 Output terminal 9 Output circuit breaker 2 2 UPS Tower Rack Installation Only available for Rack UPS Rack mount Installation This UPS can be mounted in the 19 rack chassis Please follow below steps to position this UPS Step 1 Step 2 Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Em...

Страница 10: ...ttery wires for safety consideration Before installing the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Remove front panel Connect the AC input and re connect battery wires Put the front panel back to the unit Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas...

Страница 11: ...ommunication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 5 T...

Страница 12: ...ull out the battery box by removing two screws on the front panel Step 4 Step 5 Step 6 Remove the top cover of battery box and replace the inside batteries After replacing the batteries put the battery box back to original location and screw it tightly Re connect the battery wires Step 7 Put the front panel back to the unit 2 5 Battery kit assembly Option for Rack UPS NOTICE Please assemble batter...

Страница 13: ...wing below chart Step 3 Put assembled battery packs on one side of plastic shells and insert one more dummy battery on the space Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Tapes Tapes Tapes Dummy battery Tapes Tech Novitas FZC P O BOX No 8073 S...

Страница 14: ...ect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well Tapes Tapes Tapes Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at suppo...

Страница 15: ...pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS s...

Страница 16: ...verload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is working Battery information Indicates the Battery level by 0 25 26 50 51 75 and 76 100 Indicates t...

Страница 17: ...ameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program 01 Output voltage setting Interface Setting Parameter 3 Output voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 200 presents output voltage is 200Vac 208 presents output voltage is 208Vac 220 pr...

Страница 18: ... CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable Default 05 ECO voltage range setting Interface Setting Parameter 2 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing ...

Страница 19: ... setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage point For 200 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac Default 170Vac For 100 110 115 120 127 VAC models 95 110 setting the low voltage point in parameter 3 from 95Vac to 110Vac Default 95Vac 8 Autonomy limitation setting Interface ...

Страница 20: ...requency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every ...

Страница 21: ...con flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connected Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every second Out of bypass voltage range Sounding every second Bypass frequency unstable Sounding every second EEPROM error Sound...

Страница 22: ...onnected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS output After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously so...

Страница 23: ...t be replaced In this case please contact your dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months 1 2 hours Be sure to deliver the spent battery to a...

Страница 24: ... to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Battery Mode 83 87 88 BATTERY Standard Model Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers 2 4 6 Recharge Time 4 hours recover to 90 capacity Typical Charging Current 1 0 A max Charging Voltage 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 Long run Model Battery Numbers 2 3 4 6 8 6 8 Charging Cu...

Страница 25: ...inear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Battery Mode 83 87 88 BATTERY Standard Model Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers 2 4 6 Recharge Time 4 hours recover to 90 capacity Typical Charging Current 1 0 A max Charging Voltage 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 Long run Model Battery N...

Отзывы: