For 100/110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 3:
Enable or disable Bypass function. You may
choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high voltage point
and acceptable low voltage point for Bypass mode by
pressing the Down key or Up key.
HLS:
Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264:
setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
115-132:
setting the high voltage point in parameter 3
from 115Vac to 132Vac(Default: 132Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220:
setting the low voltage point in parameter 3
from 170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
95-110:
setting the low voltage point in parameter 3 from
95Vac to 110Vac. (Default: 95Vac)
8: Autonomy limitation setting
Interface
Setting
Parameter 3:
Set up backup time on battery mode for
general outlets.
0-999:
setting the backup time in minutes from 0-999 for
general outlets on battery mode.
0:
When setting as “0”, the backup time will be only 10
seconds.
999:
When setting as “999”, the backup time setting will
be disabled. (Default)
00: Exit setting