1.  INTRODUCTION 

The  electronic  transmitters  CP420L  and  CH420L  are  designed  to  work  with  Tecfluid’s 
volumetric counters (COVOL) and turbines. The instruments are supplied already configured 
for the type of input. 

The circuit is based on a microprocessor that, in function of the pulses per litre programmed, 
calculates  the  flow  rate  and  totalizes  the  volume  that  flows  through  the  meter  and  shows 
these values on a local indicator. 

The CH420L differs from CP420L in that it is also HART protocol compatible. 

2.  OPERATION 

To adapt the transmitter to the meter, the pulses per litre factor specified on the meter must 
be programmed. To do this, the plastic front cover must be removed by unscrewing the four  
screws on the corners. After that, the push buttons will be accessible.  

If  the  instrument  has  not  been  previously  programmed  or,  due  to  an  alteration  in  the    data 
memory  the  instrument  recovers  the  default  factory  values,  then  the  display  will  show 
“PRESET”.  This  indication  will  disappear  when  the  programming  sequence  has  been 
completed. 

There are three push buttons with the following functions: 

2.1. Programming 

In all the programming screens, the “RESET” push button exits the screen without saving 
the data in the memory, even if changes in the digits have been made or not . 

By pushing the two push buttons PROG at the same time, the display will change to the 
programming  mode.  In  this  mode  there  are  7  digits  (four  whole  numbers  and  three 
decimals).  The  value  that  must  be  introduced  is  the  pulses  per  litre  factor  given  on  the 
label of the COVOL or Turbine.  

To do this, pushing the push button marked with the arrow pointing upwards, the blinking 
digit  will  increase.  Once  the  desired  value  of  the  digit  is  achieved,  by  pressing  the  push 
button  marked  with  the  arrow  pointing  left,  the  cursor  will  pass  to  the  next  digit  to  be 
modified. On the seventh digit, by pressing this push-button the cursor will pass to the first 
digit on the display. 

When the value of the pulses per litre is correct, by pushing the two push buttons PROG 
at the same time, this value will be automatically saved in the memory and it will appear the 
units selection screen. 

Содержание CP420L

Страница 1: ...Programmable flow rate transmitter CP420L CH420L Instructions Manual R MI CH420L Rev 0 English version instrumentation for fluids ...

Страница 2: ...will disappear when the programming sequence has been completed There are three push buttons with the following functions 2 1 Programming In all the programming screens the RESET push button exits the screen without saving the data in the memory even if changes in the digits have been made or not By pushing the two push buttons PROG at the same time the display will change to the programming mode ...

Страница 3: ...ing In the first screen we program the flow rate equivalent to 4 mA lower range The measuring units will be the ones chosen in the previous screen The push buttons have the same function as the pulses per litre programming After that we program the flow rate equivalent to 20 mA upper range In a CH420L if during the programming sequence we receive a HART command that must be attended the local prog...

Страница 4: ... in the instrument Example 1 Shortage of volume If we have a flow meter body which specifies i l 1 985 and when we check the volume of a batch we find that instead of having 100 litres as programmed we only have 95 litres 5 less and we must apply the following correction i l Original Pulses per litre Factor 1 985 V Expected Volume 100 Vr Real Volume 95 i l n i l V Vr i l n New Pulses per litre Fac...

Страница 5: ... 4 20 mA analog Number of Device Variables 2 Number of Dynamic Variables 1 Mappable Dynamic Variables No Number of Common Practice Commands 13 Number of Device Specific Commands 2 Bits of Additional Device Status 12 Alternative operating modes No Burst mode No Write Protection Yes Analog loop electrical characteristics for communications Reception Impedance Rx 8 5 Mȍ Cx 200 pF 4 PUSH BUTTON INHIBI...

Страница 6: ... 7 Size of the digit 8 mm Reset By means of push button 8 3 Flow rate Indication N of digits 5 Size of the digit 5 mm 8 4 General characteristics Ingress protection IP65 Ambient temperature range 0 60 ºC 8 5 Input terminals Terminal n COVOL Turbine 1 Common Ground 2 Live Live 3 Live 8 6 Inputs characteristics NOTE The input terminals are not isolated from the 4 20 mA loop Under no circumstances ca...

Страница 7: ...frequency is 0 06 Hz 8 6 2 Turbine The turbine input is designed for connecting to the coil of a magnetic pick up The input impedance is 1 2 K This input is protected to limit the maximun applied voltage to the circuit This protection consists of two diodes in parallel and two 100 Ohm resistors The maximum voltage that can be applied to the input is 10 Vpp Voltages higher that this can cause damag...

Страница 8: ...ch have not damaged due to misuse being excluded all responsibility due to any other damage or the effects of wear caused by the normal use of the devices Any consignment of devices for repair must observe a procedure which can be consulted in the website www tecfluid fr After Sales section All materials sent to our factory must be correctly packaged clean and completely exempt of any liquid greas...

Отзывы: