Establishing the System Maximum Flow Temp
Switch on the power to the TEC 100/200.
1.
Set
the
Bypass Switch
to the bypass position.
Allow the heating system to cycle twice at the normal winter setting of the
boiler thermostat (see plant engineer, caretaker, maintenance manger etc to
establish winter thermostat position).
2.
The display will show:
FIRING Tu 10:05
S57 F50 R42 E05
Current Mode
Set Temp
Actual Flow Temp
Actual Return / HW Temp
Actual External Temp
3.
When
the
actual
Flow Temperature
exceeds the
Set Temperature
, the display
will
change:
TEMP.SET Tu 10:05
S57 F58 R48 E05
4.
When the boiler has cycled twice with the TEC 100/200 in
bypass
, observe the
actual
flow
temperature
as shown on the display:
In this example, the winter setting for the heating system (TEC 100/200
maximum flow setting) should be set to 72ºC (73ºC - 1ºC).
The Boiler Thermostat should now be set to a higher setting to ensure correct
operation of the TEC 100/200.
TEMP.SET Tu 10:05
S57 F73 R65 E05