16.
LOW EXTERNAL SET RANGE
Write Command:
20 hex
Read Command:
54 hex
Interpret:
Value
mapped
to zero voltage of Input2.
17.
HIGH EXTERNAL SET RANGE
Write Command:
21 hex
Read Command:
55 hex
Interpret:
Value mapped to 5 volt or maximum voltage of Input2.
18.
ALARM DEADBAND
Write Command:
22 hex
Read Command:
56 hex
Interpret:
Temperature
Input1 must move to toggle
alarm
output.
19.
HIGH ALARM SETTING
Write Command:
23 hex
Read Command:
57 hex
Interpret:
Temperature
reference
to compare against Input1 for high
alarm
output.
20.
LOW ALARM SETTING
Write Command:
24 hex
Read Command:
58 hex
Interpret:
Temperature
reference
to compare against Input1 for low
alarm
output.
21.
CONTROL DEADBAND SETTING
Write Command:
25 hex
Read Command:
59 hex
Interpret:
Temperature
or
count
span Input1 must move to toggle
control
output.
22.
INPUT1 OFFSET
Write Command:
26 hex
Read Command:
5a hex
Interpret:
Value to offset Input1 by in order to calibrate external
sensor
if
desired.
23.
INPUT2 OFFSET
Write Command:
27 hex
Read Command:
5b hex
Interpret:
Value to offset Input2 by in order to calibrate external
sensor
if
desired.