background image

 
 
 

Tyco Electronics (UK) Ltd 
Freebournes Road, 
Witham 
Essex CM8 3AH 
England 
Tel: +44 (0) 1376 509509 
Fax: +44 (0) 1376 509511 
www.crompton-instruments.com 
www.energy.te.com 

CI-3K46701 Project 2191 rev 07 21/01/21 

Registered office: 
Faraday Road, Dorcan 
Swindon, SN3 5HH 
Reg. no. 550 926 

While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalog, TE does not guarantee 
that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. 
TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied 
warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a 
particular purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications are 
subject to change without notice. Consult TE for the latest dimensions and design specifications. TE connectivity (logo) and TE Connectivity are 
trademarks of the TE Connectivity Ltd. family of companies. Other logos, product and company names mentioned herein may be trademarks of 
their respective owners. Crompton is a trademark of Crompton Parkinson and is used by TE Connectivity under a licence.  

 

Auxiliary Supply 

Two-way fixed connector with 2·5mm

(12AWG) stranded wire 

capacity.  110 to 400V a.c. 50/60Hz ±10% or 120V to 350V d.c. 
±20%.  Consumption < 10W. 

 

Pulse Relay Output 

The pulse relay output can be set to generate pulses to represent 
imported kWh, exported kWh, imported kVArh or exported kVArh. 

Rate

 can be set to generate 1 pulse per: 

0·001  = 1 Wh/VArh 
0·01 

= 10 Wh/VArh 

0.1 

= 100 Wh/VArh 

= 1 kWh/kVArh 

10 

= 10 kWh/kVArh 

100 

= 100 kWh/kVArh 

1k 

= 1 MWh/MVArh 

10k 

= 10 MWh/MVArh 

The  rate  cannot  be  set  to  a  value  that  could  result  in  more 
than 2 pulses per second. 

Pulse width

 200/100/60 ms. 

 

Relay Rating

 240V ac 50mA 

 

RS485 Output for Modbus or JC N2 Protocol 

For  Modbus  protocol,  the  following  RS485  communication 
parameters can be configured from the Set-up menu: 

Baud rate

 2400, 4800, 9600, 19200, 38400 

Parity

 none/odd/even 

Stop bits

 1 or 2 

RS485 network address

 

nnn

 

– 3-digit number, 1 to 247 

Modbus Word order

  Shows the word order (Hi/Lo) of the 8-bit 

bytes in the Modbus message format.  This setting can only be 
changed from the Modbus port. 

Note that with odd or even parity, Stop Bits are forced to one. 

For  JC  N2  protocol,  only  the  RS485  network  address  can  be 
configured.  The range of addresses is 1 to 255. 

 

 

For technical assistance please contact your nearest Crompton 
service centre, or: 
 
Tyco Electronics (Crompton Instruments) Ltd 
Freebournes Road 
Witham 
CM8 3AH 
United Kingdom 
Tel: +44 (0) 1376 509509 
Fax: +44 (0) 1376 509511 

 

Reference Conditions of Influence Quantities 

Influence Quantities are variables that affect measurement errors to 
a minor degree.  Accuracy is verified under nominal value (within 
the specified tolerance) of these conditions. 

Ambient temperature 

23°C ±1°C 

Input waveform 

50 or 60Hz ±2% 

Input waveform 

Sinusoidal (distortion factor <0·005) 

Auxiliary supply voltage 

Nominal ±1% 

Auxiliary supply frequency 

Nominal ±1% 

Auxiliary supply waveform 
(if AC) 

Sinusoidal (distortion factor <0·05) 

Magnetic field of external 
origin 

Terrestrial flux 

 

Environment 

Operating temperature 

-10°C to +55°C

*

 

Storage temperature 

-20°C to +70°C

*

 

Relative humidity 

0 to 90%, non-condensing 

Altitude 

Up to 2000m 

Warm up time 

1 minute 

Vibration 

10Hz to 50Hz, IEC 60068-2-6, 2g 

Shock 

30g in 3 planes 

*

Maximum operating and storage temperatures are in the context of 

typical daily and seasonal variation. 

 

Mechanics 

DIN rail dimensions 

72 x 90 mm (WxH) per DIN 43880 

Mounting 

DIN rail (DIN 43880) 

Sealing* 

IP20 (minimum) 

Material 

Self-extinguishing UL 94 V-0 

*Not evaluated by UL 

 

Approval, Certification, and Standards Compliance 

RoHS compliant.  (Although this class of product is presently 
excluded from the RoHS regulations, the unit has been designed 
and manufactured in compliance with the RoHS regulations.) 

EMC Emissions

 

BS EN 61326, Class A (Industrial) 

EMC Immunity

 

BS EN 61326, Class A (Industrial) 

Safety

 

BS EN 61010-1 

 

UL61010-1 

 

 

 

 

 

 

 