Installation 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Case Dimensions: 

Width 71·3 mm, Depth 57·5 mm, Length 90·5 mm   
Length including fixing tag 93·5 mm. 

The unit is intended for mounting on a standard DIN rail within a 
suitable metallic or flame proof enclosure (IP2X minimum) such that 
only the front face (display) can be accessible in normal use.  Avoid 
mounting the unit where there is excessive vibration; in excessive 
direct sunlight; or outside a reasonably stable ambient temperature 
of -10 to +55°C 

 

Safety 

The unit is designed in accordance with BS EN 61010-1:2001 
(IEC 61010-1:2001) 

– Permanently connected use, Normal 

condition.  Installation category III, pollution degree 2, basic 
insulation for rated voltage.  Measurement Category III. 

 

 

 

EMC Installation Requirements 

Whilst this unit complies with all relevant EU EMC (electro-magnetic 
compatibility) regulations, any additional precautions necessary to 
provide proper operation of this and adjacent equipment will be 
installation dependent and so the following can only be general 
guidance: 

 

Avoid routing wiring to this unit alongside cables and 
products that are, or could be, a source of interference. 

 

The auxiliary supply to the unit should not be subject to 
excessive interference.  In some cases, a supply line filter 
may be required. 

 

To protect the product against incorrect operation or 
permanent damage, surge transients must be controlled.  
It is good EMC practice to suppress transients and surges 
at the source.  The unit has been designed to 
automatically recover from typical transients; however in 
extreme circumstances it may be necessary to temporarily 
disconnect the auxiliary supply for a period of greater than 
5 seconds to restore correct operation. 

 

Screened communication leads are required.  These and 
other connecting leads may require the fitting of RF 
suppression components, such as ferrite absorbers, line 
filters etc., if RF fields cause problems. 

 

It is necessary to wind the three current inputs through 
separate ferrite rings an example part number Wurth 742 
701 110, a minimum of 6 times. 

 

It is good practice to install sensitive electronic instruments 
that are performing critical functions in EMC enclosures 
that protect against electrical interference causing a 
disturbance in function. 

 

Wiring 

Input connections are made to screw clamp terminals.  Choice of 
cable should meet local regulations for the operating voltage and 
current. Terminals are suitable for Copper wire only, 0.05-2.5mm² 
(30-12AWG). Recommended tightening torque 0.5/0.6Nn (4.4/5.3 
Lbf in) For UL approved installations wiring should conform to 
National Electrical Code (NEC) Class 1, rated 600V / 60°C 
minimum. 

The current inputs of these products are designed for 
connection into systems via current transformers only, 
conforming to IEC 60044-1 or ANSI / IEEE C57.13 

All negative current inputs are commoned inside the unit and 
grounding should be at one point only.  To minimise measurement 
errors, the CTs should be grounded as shown in the wiring 
diagram. 

CT secondaries must be grounded in accordance with local 
regulations.  It is desirable to make provision for shorting links to be 
made across CTs to permit easy replacement of a unit should this 
ever be necessary. 

Additional considerations for three wire systems 

The neutral terminal (terminal N) is indirectly connected to the 
voltage input terminals (terminals L1, L2, L3).  When connected to 
a three wire system the neutral terminal will adopt a potential 
somewhere between the remaining lines. 

If external wiring is connected to the neutral terminal it must be 
connected to either the neutral line or earth (ground) to avoid the 
possibility of electric shock from the neutral terminal. 

 

 

 Danger: Risk of Elecric Shock

            

 

During normal operation, voltages hazardous to life may 
be present at some of the terminals of this unit.  
Installation and servicing should be performed only by 
qualified, properly trained personnel abiding by local 
regulations.  Ensure all supplies are de-energised before 
attempting connection or other procedures. 

 

Terminals should not be user accessible after installation 
and external installation provisions must be sufficient to 
prevent hazards under fault conditions. 

 

This unit is not intended to function as part of a system 
providing the sole means of fault protection - good 
engineering practice dictates that any critical function be 
protected by at least two independent and diverse 
means. 

 

The unit does not have internal fuses therefore external 
fuses must be used for protection and safety under fault 
conditions. 

 

Never open-circuit the secondary winding of an 
energised current transformer. 

 

This product should only be operated with the CT 
secondary connections earthed. 

 

If this equipment is used in a manner not specified by the 
manufacturer, protection provided by the equipment may 
be impaired. 

 

Auxiliary circuits (communication & relay outputs) are 
separated from metering inputs and 110-400V supply 
circuits by at least basic insulation.  Any equipment 
connected to these auxiliary circuits that may be 
accessible in normal use, should provide supplementary 
insulation rated 400Vrms minimum between auxiliary 
circuits and any accessible parts, such that at least basic 
insulation is maintained under fault conditions.  The 
connection at the remote end of such auxiliary circuits 
should not be accessible in normal use.  Depending on 
application, equipment connected to auxiliary circuits 
may vary widely.  The choice of connected equipment or 
combination of equipment should not diminish the level 
of user protection specified in the end use application. 