background image

Installation and 

Operating Instructions 

 

Integra Ri3 

 

DIN-rail digital meter for single 

and three-phase electrical systems 

 

 

Caution: 

consult instructions before installation or use

 

 
 
 
 
 
 
 

 

Introduction 

This unit measures and displays the characteristics of single-phase 
two-wire, three-phase three-wire and three-phase four-wire 
supplies, including voltage, frequency, current, power and real and 
reactive energy, imported and exported. 

For more in-depth operating instructions, please refer to the full 
manual that is available on the Crompton Instruments website, at 

www.crompton-instruments.com

 

Measurement 

In measurement mode, the buttons control the displayed 
measurement as follows: 

 

Selects the Voltage and Frequency display screens.  
Successive operations of the button select voltage, 
frequency and %THD (Total Harmonic Distortion). 
In Set-

up mode, this is the ‘Back’ button. 

 

Selects the Current display screens.  Successive 
operations select phase and neutral (3ph4w) currents, 
max. demanded currents and current %THD. 
In Set-

up mode, this is the ‘Up’ button. 

 

Selects the Instantaneous Power screens.  Successive 
operations select power (W, VAr & VA), max. 
demanded power and power factor. 
In Set-

up mode, this is the ‘Down’ button. 

 

Selects the Energy display screens.  Successive 
operations select imported/exported Wh and Varh. 
Display can indicate up to 9999999·9. 
Running man symbol flashes as data accumulates. 
1% symbol shows that power values of <1% of range 
maximum will be included in energy readings. 
In Set-

up mode, this is the ‘Enter’ button. 

 

Display shows the units of measurements in use for each range.  
Energy units can be set via set-up screens; other units are set 
automatically. 

A Demand Reset resets maximum demand readings to zero. 

 

Setting up 

To enter set-up mode, firmly press the 

 and 

 buttons 

simultaneously and hold for 5 seconds, until the password screen 
appears.  Setting up is password-protected so you must enter the 
correc

t password (default ‘0000’) before proceeding.  If an incorrect 

password is entered, the display reverts to measurement mode. 

To exit setting-up mode, press 

 repeatedly until the 

measurement screen is restored or hold 

 and 

 buttons 

simultaneously for 5 seconds. 

Setup Menu Structure 

Change password

 

nnnn

 

– 4-digit number, default ‘0000’. 

Supply system 

3-phase 3-wire or 4-wire or single phase. 

CT

  Set the value of the CT primary in use 

nnnn

 

– 4-digit number, 0001 to 9999. 

dIT - Demand Integration Time 

This is the period in minutes over which the current and power 
readings are integrated for maximum demand measurement.  
Options are: Off, 5, 8, 10, 15, 20, 30 and 60 minutes. 

RSET

 

Resets cumulative Energy and/or Demand 
measurements to zero. 

COMS 

Communication parameters for RS485 interface: 

FMT

 

– Format: 

Modb

  Modbus protocol, 

Baud rate 2400/4800/9600/19200/38400 
Parity none/odd/even 
Stop bits 1 (1 or 2 if parity is None) 
Network address 

nnn

 

– 3-digit number, 1 to 247 

Order: Norm/Rev 

– Indicates Modbus word order. 

N2

 

Johnson Controls (JC) N2 protocol, 

Network address 

nnn

 

– 3-digit number, 1 to 255. 

Rly - Relay pulse output

 

kWh/kVArh (Active/reactive) Import or Export 
Rate 0.001/0.01/0.1/1/10/100/1k/10k kWh or kVArh per pulse 
Pulse width 200/100/60 ms. 

NRGy - Energy 

Unit/kilo/Mega units selection 
1% limit on/off.  If 

on,

 power values <1% of range max. will not 

be included in energy measurements (prevents ‘creep’). 

Test 

Display on 

– all elements on to check display 

dISTG 

– Display toggle.  Each element is turned on and off 

Phase sequence (V123 I123). 

SOFT 

Displays firmware version and build numbers. 

 

Menu Option Selection 

1.

 

Use the 

 (up) and 

 (down) keys to select the required 

item from the menu.  Selection does not roll over between 
bottom and top of list. 

2. 

Press 

 to confirm the selection.

 

3. 

If an item flashes, then it can be adjusted by the 

 (up) and 

 (down) keys.  If not, there may be a further layer, e.g. 

Comms - Baud rate, before adjustment is possible.  Press 

 to select the lower layer.

 

4. 

Having selected an option from the current menu layer, press 

 to confirm your selection.  The SET indicator will appear.

 

5. 

Having completed a parameter setting, press 

 to return to 

a higher menu level.  The SET indicator will be removed and 

you will be able to use the 

 and 

 keys for further 

menu selection. 

6. 

On completion of all setting-up, press 

 repeatedly until the 

measurement screen is restored. 

 

Number Entry Procedure 

When setting up the unit, some screens require the entering of a 
number.  In particular, on entry to the setting up section, a 
password must be entered.  Digits are set individually, from left to 
right.  The procedure is as follows: 

1. 

The current digit to be set flashes and is set using the   

 

 (up) and 

 (down) keys.

 

2. 

Press 

 to confirm each digit setting. The SET indicator 

appears after the last digit has been set. 

3. 

After setting the last digit, press 

 to exit the number 

setting routine. The SET indicator will be removed. 

 