3-13. Withstand Voltage 

This  series  is  designed  to withstand  3.0kVAC  between input 
and  output,  2.0kVAC  between  input  and  PE  (Chassis)  and 
500VAC between output and the PE (Chassis) each for 1 mi-
nute. When performing this test, set current limit of the with-
stand voltage test equipment to 20mA ( Output - PE (Chassis) : 
100mA  ).  The  applied  voltage  must  be  gradually  increased 
from  zero  to  the  test  value  and  then  gradually  decreased  for 
shut  down.  When  timer  is  used,  the  power  supply  may  be 
damaged by high impulse voltage during timer switch on and 
off. Connect input and output as follows. 
 
Input ~ Output (dotted line ) 

3kVAC 1min. ( 20mA ) 

Input ~ PE (Chassis) (solid line ) 
             2kVAC 1min. ( 20mA ) 
 

           

 

AC(L) 

AC(N) 

           +V1 

              G1 

FG 

   +V2 

   G2 

Withstand 
Voltage 
Tester 

              +R 

              -R 

 

 
 
Output ~ PE (Chassis) 

500VAC 1min. ( 100mA ) 

            
 
 

 

AC(L) 

AC(N) 

         +V2 

            G2 

FG 

    +V1 

  G1 

Withstand 
Voltage 
Tester 

             +R 

             - R 

 

 

 
 

3-14. 

External  connection  of  circuit  with  protective 

seperation

 

 
All the outputs is protected using protection of SELV. ( As per 
required in the EN50178, clause 5.2.8) 
 
 

3-15. 

Max Current during abnormal 

 

 

The Max output current of CH1 under any abnormal situation 
is 9.39 A (DC) 
The Max output current of CH2 under any abnormal stituation 
is 16.52 A   (DC) 
 

 
3-16. Climatic condition 
 

This product is certified to the Climatic condition, Type B of 
the EN50178. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 
 
 
 
 
 

PE 

PE 

Содержание ZWD150PAF Series

Страница 1: ...uld result in damage There is no possibility of fire or burning Confirm that connections to input output terminals are correct as indicated in the instruction manual This power supply is PC board type...

Страница 2: ...ut Voltage adjust trimmer VR1 The 5V Output voltage rises when the trimmer is turned clockwise V ADJ 24V Output Voltage adjust trimmer VR2 The 24V Output voltage rises when the trimmer is turned clock...

Страница 3: ...terminal V ADJ 5V Output Voltage adjust trimmer VR1 The 5V Output voltage rises when the trimmer is turned clockwise V ADJ 24V Output Voltage adjust trimmer VR2 The 24V Output voltage rises when the...

Страница 4: ...nal G1 CH1 ve Output terminal V2 CH2 ve Output terminal G2 CH2 ve Output terminal V ADJ 5V Output Voltage adjust trimmer VR1 The 5V Output voltage rises when the trimmer is turned clockwise V ADJ 24V...

Страница 5: ...terminal of the equipment Output current of each connector pin must be less than 5A Except T model which M4 screw is used The output load line and input line shall be separated and twisted to improve...

Страница 6: ...5 TDK Lambda ZWD150PAF Series INSTRUCTION MANUAL ZWD150PAF J ZWD150PAF T...

Страница 7: ...wn Manual reset or input voltage recycling is needed for output recovery 3 5 Over Current Protection OCP OCP type is constant current limiting with automatic recovery OCP function operates when the ou...

Страница 8: ...y 10 C if 35 duty operation is required Vin VAC Ip max Duty max t sec 85 132 10A 35 10sec 170 265 10A 35 10sec 170 265 12A 20 5sec 4 Formula ZWD150PAF Io ave Ip x D Im x 1 D Io spec refer to derating...

Страница 9: ...voltage during timer switch on and off Connect input and output as follows Input Output dotted line 3kVAC 1min 20mA Input PE Chassis solid line 2kVAC 1min 20mA AC L AC N V1 G1 FG V2 G2 Withstand Volta...

Страница 10: ...rve In the following de rating curve average load is percent of maximum output load both Maximum Output Current and Maximum Output Power in specifications Do not exceed the load deratings PCB type A W...

Страница 11: ...Forced air Average Load Mounting Ta A B C D E 10 60 C 100 70 C 50 With chassis and cover type Forced air Average Load Mounting Ta A B C D E 10 50 C 100 60 C 50 Recommended minimum air velocity 0 7m s...

Страница 12: ...be connected to the earth terminal of the apparatus If not the EMI noise and output noise will increase Hatching area is maximum permissible area of metal part for mounting For chassis option L chassi...

Страница 13: ...he ac tual load condition ZWD150PAF T5AH 7 Before concluding that the unit is at fault Before concluding that the unit is at fault make the following checks Check if the rated input voltage is connect...

Отзывы: