8
4.3 SCPI Subsystem Commands
Subsystem commands control all Z
+
functions. For a full command description refer to section
7.12 in Z
+
series User Manual. Short list of Z
+
series commands:
SCPI Command
Description
ABORt
Aborts the triggered action
DISPlay
[:WINDow]:STATe <bool>
Display ON/OFF*
[:WINDow]:FLASh <bool>
Display Flash
GLOBal
:CURRent
:[AMPLitude] <NRf+>
Set the output current for all power supplies
:VOLTage
:[AMPLitude] <NRf+>
Set the output voltage for all power supplies
:OUTPut:STATe <bool>
Enables/disables the all power supplies output
*RCL {1|2|3|4}
Recall setting for all power supplies
*RST
Reset all power supplies
*SAV {1|2|3|4}
Save settings for all power supplies
INITiate
[:IMMediate]
Trigger initiate
:CONTinuous <bool>
Enable/disable continuously trigger*
INSTrument
:COUPle ALL|NONE
Couple for all Z
+
power supplies
:NSELect <NRf>
Select the power supply for communication*
MEASure
:CURRent[:DC]?
Returns the measured output current
:VOLTage[:DC]?
Returns the measured output voltage
:POWer[:DC]?
Returns the measured output power
OUTPut
[:STATe] <bool>
Enables/disable the supply output*
:PON
[:STATe] <bool>
Programs the Power-ON state*
:PROTection
:CLEar
Resets latched protection
:FOLDback
[:MODE] OFF|CC|CV
Set operation protection mode*
:DELay <NRf+>
Set protection delay*
:ILC
:MODE <bool>
Enables/disable analog output ON/OFF control*
:TTLTrg
:MODE OFF|FSTR|TRIG
Set output trigger mode*
:RELay {1|2}
[:STATe] <bool>
Set control pins status*
:MODE?
Returns the operation mode CV/CC/OFF