5. Mounting Methed 

5-1. Mounting Method 

(1)

 

  This is convection cooling type power supply. In the consideration for the heat radiation and safety.   

Please take a distance more than 15mm between the power supply and the peripheral parts.   
When lining up multiple units, please make sure to place them 15mm or more apart from each other. 

(2)

 

  Please take insulation distance (space) more than 5mm for the component side at the open frame type. 

(3)

 

  The maximum allowable penetration of mounting screws is 6mm. 

(4)

 

  Recommended torque for mounting screw 

HWS30A/ME 

  HWS150A/ME (M3 screw) : 0.49 N

×

m ( 5.0 kgf

×

cm ) 

 
 
 
 
 
 
 
 
 
 

 
 
 

5-2. Output Derating according to the Mounting Directions 

Recommend standard mounting is direction ( A ). Direction ( B ), ( C ) and ( D ) are also possible.

 For other 

mounting 

directions, 

please inquire to TDK-Lambda. 

Refer to the derating below. Please do not use mounting direction ( E ), where the PCB will be on the topside and   
heat will be trapped inside the unit. Load (%) is percent of maximum output power or maximum output current,   
do not exceed its derating of maximum load. 
 
 

Mounting direction 

 

 
 
 
 
 
 
 
 

 

 

 

 
 
 
 
 
 
 

Standard Mounting

(A)

(B)

(C)

(D)

(E)

Not Possible

15mm or more 

Provide punching, etc. to allow air to pass. 

15mm or more 

Air flow 

Sheet Metal 

Содержание HWS ME Series

Страница 1: ...Output power ambient temperature and ambient humidity should be kept within specifications otherwise the product will be damaged Do not operate and store this product in an environment where condensa...

Страница 2: ...g parameters Material Group IIIb Pollution Degree 2 Overvoltage Category II Class I earthed Indoor use as part of an overall equipment such that the product is accessible to service engineers only EMC...

Страница 3: ...xygen or with nitrous oxide No 3 These products are classed as ordinary equipment according to IEC EN ES CSA60601 1 and are NOT protected against the ingress of water 4 The output circuit has not eval...

Страница 4: ...stment trimmer Output monitoring indicator Green LED All screws size is M3 5 HWS100A ME HWS150A ME V Output terminal 30A max terminal V Output terminal 30A max terminal FG Frame Ground L Input termina...

Страница 5: ...nt of noise sensitivity HWS30A ME HWS50A ME HWS100A ME HWS150A ME Basic connection Local sensing Connect S terminal to V terminal and S terminal to V terminal with the attached short pieces Short piec...

Страница 6: ...Power thermistor method so that higher current will flow at higher ambient temperature or re input condition Please select input switch and fuse carefully with the high temperature and re input the p...

Страница 7: ...e load terminal 2 Between S terminal and V terminal 3 Between S terminal and V terminal If remote sensing terminals are opened the output will rise and OVP may be triggered 4 7 Output Ripple Noise The...

Страница 8: ...he power supply output voltage higher by the amount of forward voltage drop VF of the diode 2 Please adjust the output voltage of each power supply to be the same 3 Please use within the specification...

Страница 9: ...o frame ground Some of the withstand voltage tester may generate high voltage at the matching with monolithic ceramic capacitor and may cause the unit damage So please check the waveform of test volta...

Страница 10: ...of mounting screws is 6mm 4 Recommended torque for mounting screw HWS30A ME HWS150A ME M3 screw 0 49 N m 5 0 kgf cm 5 2 Output Derating according to the Mounting Directions Recommend standard mounting...

Страница 11: ...WS30A ME HWS50A ME HWS100A ME Ta Load Mounting A B C D 10 50 100 60 60 70 40 Ta Load Mounting A Mounting B D Mounting C 10 45 100 100 100 50 100 100 86 60 70 65 58 70 40 30 30 Ta Load Mounting A Mount...

Страница 12: ...minal M3 5 Screws 1 0N m 10 2kgf cm 1 6N m 16 3kgf cm 6 8mm 0 8mm 2 piece HWS100A ME AWG12 22 Output terminal M3 5 Screws 1 0N m 10 2kgf cm 1 6N m 16 3kgf cm 8 1mm 1 0mm 1 piece 0 8mm 2 piece AWG14 22...

Страница 13: ...ME 3 15A HWS150A ME 5A 9 Before concluding that the unit is at fault Before concluding that the unit is at fault make the following checks 1 Check if the rated input voltage is connected 2 Check if t...

Отзывы: