TDK-Lambda HFE1600-48 Скачать руководство пользователя страница 9

1.4 ON/OFF control by INHIBIT

Power Supply operation requires the "ENABLE" signal to be connected to "Signal Return".

Logic of the "INHIBIT" signal is reversed to logic of the "ENABLE" signal.

Switch closed: Output OFF

Switch open:   Output ON

SIGNAL RETURN, INHIBIT and ENABLE controls are isolated from the output terminals and -SENSE.

1.5 OUTPUT VOLTAGE PROGRAMMING by External Potentiometer 

(Not applicable to supplies with PMBUS option).

Output Voltage of HFE1600 Series can be trimmed by potentiometer between approximately 80%-120% for 24V, 32V, 48V 

and 80%-110%  for 12V of nominal output voltage (For Output voltage limits see Graph below).

Fig-1.5

Fig-1.4

Fig 1-5

36

48

59

18

24

29

9.6

12

13.2

24

32

39.5

0

10

20

30

40

50

60

%

0

0

1

%

0

5

%

0

V OUT (V)

Viper position

Voltage Trimming by potentiometer

Fig 1-5

HFE1600-48

HFE1600-24

HFE1600-12

HFE1600-32

1.2 Basic configuration (Remote Sense)

For basic configuration:

 

± SENSE have to be connected to the ±V terminals on the Load side prior to operating the supply.

 

ENABLE input must be connected to SIGNAL RETURN in order for the supply to turn on.

ENABLE

B7

-SENSE

Voltage drop

on load connection

+V

+SENSE

A6~10

B9

B4

-V

A1~5

HFE1600

LOAD

+V

-V

B1

SIGNAL RETURN

Voltage drop

on load connection

Fig-1.2

ATTENTION:  1. Maximum voltage drop on load connection: HFE1600-12: 0.25V/wire, HFE1600-24: 0.5V/wire,

HFE1600-32: 0.75V/wire, HFE1600-48: 1V/wire.

 

2. Twisted wires should be used for Remote Sensing connection.

 

3. If Remote Sensing is used, do not break Main Output connection.

1.3 ON/OFF control by ENABLE

ENABLE

B7

HFE1600

B1

SIGNAL RETURN

Switch closed: Output ON

Switch open:   Output OFF

Fig-1.3

SIGNAL RETURN and ENABLE control are isolated from the output terminals and “-SENSE”.

9

Содержание HFE1600-48

Страница 1: ...Instruction Manual 27 Over temperature protection Inverter shut down automatic restart 28 Remote On Off control Two complementary inputs By electrical signal or dry contact Refer to instruction manual...

Страница 2: ...um output power by 5 10 Inverter shut down method Reset by recycle AC voltage or by On Off control 11 Measured with JEITA RC9131A 1 1 probe using 470 F electrolytic capacitor and 0 1 F film capacitor...

Страница 3: ...HFE 1600 12 24 48 Series HFE 1600 12 24 48 Series Fig B Output Power derating at temp 60 C Fig C Output Power derating at temp 70 C Pout 1500W 1200W 1100W 1000W Vin 85Vac All Output Voltages Fig A1 Ou...

Страница 4: ...L RETURN B14 NC B2 PS EXIST B15 DC OK B3 AUX_OUT 12V B16 NC B4 SENSE B17 NC B5 NC B18 TEMP ALARM B6 CURRENT SHARE B19 V REFERENCE OUT B7 ENABLE B20 NC B8 VOLTAGE ROGRAMMING B21 AC FAIL B9 SENSE C1 CHA...

Страница 5: ...act 0 0 6v or short SIGNAL RETURN B8 VOLTAGE PROGRAMMING Input 0 5V referenced to S Provides Vout programming by Voltage Refer to Instruction Manual Chapter 1 5 1 6 SENSE B9 SENSE Positive sense The S...

Страница 6: ...d for use in the following operation conditions Indoor use Pollution degree 2 Max operational altitude 3000m above sea level Ambient temperature 10 C 50 C at 100 load up to 70 C with output de rating...

Страница 7: ...tage fluctuations should not exceed 10 of nominal voltage HEAT HAZARD WARNING Top bottom and side surfaces may become hot when operating the unit continuously To reduce the risk of injury from a hot s...

Страница 8: ...L RETURN in order for the supply to turn on V A6 10 V A1 5 SENSE B9 SENSE B4 ENABLE B7 HFE1600 V V B1 SIGNAL RETURN LOAD Fig 1 1 1 2 FRONT PANEL INDICATORS 1 DC OK LED indicator GREEN when Output Volt...

Страница 9: ...n Voltage Trimming by potentiometer Fig 1 5 HFE1600 48 HFE1600 24 HFE1600 12 HFE1600 32 1 2 Basic configuration Remote Sense For basic configuration SENSE have to be connected to the V terminals on th...

Страница 10: ...0mA shunted by internal 24V zener isolated from Output and referenced to SIGNAL RETURN Fig 1 8 Open collector signals are shunted by internal 24V zener 1 6 OUTPUT VOLTAGE PROGRAMMING by External Volta...

Страница 11: ...ignal between the paralleled units automatic current balance is achieved with accuracy of Accuracy 10 20 Iout 50 of max Iout Up to 10 units Accuracy 5 Iout 50 of max Iout Up to 10 units Derate the tot...

Страница 12: ...of positive unit and Sense of negative unit twisted pair to Load point or to V and V accordingly for Local Sense Output Voltage can be adjusted independently for each unit Controls Monitoring signals...

Отзывы: