9. Fan Life Expectancy. 

The fan life has limitation. Therefore, periodic maintenance by exchanging the life-expired fan is required for the power 
supply. The following figure shows the life of fan. 
 

 

 
Measurement point of fan exhausts temperature 

 
 
 
 

 

 

10. Before concluding that the unit is at fault, Please make the following checks. 

(1)    Check if the rated input voltage is connected and within specification. 
(2)

 

Check if the wiring of input and output is correct. 

(3)

 

Check if the I/O terminal connection is properly tightened by required torque. 

(4)

 

Check if the wire thickness is enough. 

(5)

 

Check if the output voltage trimmer (V.ADJ) is properly adjusted.  OVP might be triggered and output is  
shutdown. 

(6)

 

Is the chassis of power supply abnormally hot? The output is shutdown by OTP operation. Please disconnect or 
turn off the AC input and let the unit cool down sufficiently before turning ON the AC input again. 

(7)

 

Check if the output current and output wattage does not exceed the specification. 

(8)

 

Audible noise may be heard when input voltage waveform is not sinusoidal. 

(9)

 

Audible noise may be heard during dynamic load operation. 

(10)

 

Ensure that a large capacitor is not connected across the output terminals. Please use within maximum 
capacitance shown below. 

 

 

Maximum external capacitance 

MODEL 12V 24V 36V 48V 
GWS500 10,000uF 

5,000uF 

1,000uF 

 

 
      Air Flow 
          P.S. 

50mm 

Temperature  
measurement point 

FRONT SIDE 

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Содержание GWS 500 Series

Страница 1: ...and notify in the system instruction manual Never operate the unit under over current or short circuit conditions for more than 30 seconds or outside its specified Input Voltage Range which could res...

Страница 2: ...stment trimmer The output voltage rises when the trimmer is turned clockwise 8 CN201 Remote Sensing DCOK 5VSB Remote On Off and PV signals Refer to 2 2 1 blank Standard type BAT Battery charging for 2...

Страница 3: ...is output is not controlled by the remote ON OFF control 8 5V COM Return loop for 5VSB output 9 CNT Remote ON OFF control terminal When CNT is pulled to TTL low power supply unit turns ON Otherwise it...

Страница 4: ...ct S terminal to terminal of load and S terminal to terminal of load with sensing wires The total line voltage drop side line and side line shall be less than 0 3V In case that sensing lines are too l...

Страница 5: ...or use shielded wires Remote ON OFF control lines shall be twisted or use shielded wire Current for each terminal screw shall be 40A or less Basic Connection Local Sensing Connect with the attached co...

Страница 6: ...then re input Alternatively use CNT reset Remote ON OFF OFF to ON OVP setting is fixed and cannot be adjusted externally 4 4 Over Current Protection OCP OCP function operates when the output current e...

Страница 7: ...while the output is turned OFF when these terminals are opened When this function is not used connect CNT and CNT terminals together The specifications for this function are as follows 1 TTL compatibl...

Страница 8: ...A Method B 4 10 Parallel Operation A Operation to increase the Output Current is not possible B Operation as a Backup Power Supply is possible as follows 1 Set the power supply output voltage higher...

Страница 9: ...el limit output voltage variation range at 80 120 At PV voltage variation 4V 6V Connection method PV voltage Nominal Input Voltage Output Voltage Linearity 12V 24V 36V 48V 5 5V 6V 5V Nominal Vout 0 60...

Страница 10: ...elow 24 BAT should be used to charge 24V battery while 48 BAT should be used to charge 48V battery Battery charging Constant Current is applicable for valid output voltage range The unit may hiccup be...

Страница 11: ...n the specified voltage range is present 4 15 Output Dynamic Load Response During output dynamic load test from no load condition the output voltage level might experience a higher voltage dip of 15 t...

Страница 12: ...rrent limit of withstand voltage test equipment at 20mA Output chassis 100mA The applied voltage must be gradually increased from zero to testing value and then gradually decreased for shut down When...

Страница 13: ...at least 15cfm and air blowing out from the opposite side of the input output connectors 70 50 Airflow 15 cfm OUTPUT DERATING CURVE 0 20 40 60 80 100 120 25 0 25 50 75 100 Ta o C LOAD MOUNTING A B 70...

Страница 14: ...rse case temperature rise the selected measurement point should not face direct airflow and the equipment powered should operate under worse case operating conditions 1 Absolute temperature Maximum te...

Страница 15: ...terminal The recommended wire type MODEL Recommended Wire Recommended torque Recommended crimp type terminal D Max T Max Mounting Pieces Max GWS500 AWG18 10 M4 Screws 1 27 N m 13 kgf cm 6 8mm 0 8mm 4...

Страница 16: ...disconnect or turn off the AC input and let the unit cool down sufficiently before turning ON the AC input again 7 Check if the output current and output wattage does not exceed the specification 8 A...

Страница 17: ...method Standard installation Following cases will not be covered by warranty 1 Improper usage and mis handling like dropping or applying shock to the unit and defects from operation exceeding specific...

Отзывы: