FPS
A-50
・All specifications are subject to change without notice.
ITEMS/UNITS
MODEL
FPS-S1U
Input
Voltage Range
(*2) V
AC85 - 265 continuous (Universal input)
Frequency
(*2) Hz
47 - 63, Single phase
Current (100/200VAC)(max)
A
12.0 / 6.0 for each FPS1000 unit installed
Output Maximum Power
(*1) W
3000
Function
Remote Sensing
(*3)
Possible.
Remote ON/OFF Control
Separate control for each FPS1000 unit, by electrical signal or dry contact.
On: 0 - 0.6V or short. OFF: 2 - 15V or open.
Parallel Operation
(*6)
Possible.
Series Operation
(*4)
Possible. Up to 2 racks of the same voltage and current rating.
Over Temperature Alarm
Signal
Separate control for each FPS1000 unit, open collector signal.
Normal: ON, max.sink current: 10mA
DC OK Signal
Separate control for each FPS1000 unit, open collector signal.
On when Vout>80%+/-5% max.sink current: 10mA
AC Fail Signal
Separate control for each FPS1000 unit, open collector signal.
On when Vin > 85VAC, max.sink current: 10mA.
AUX-BIAS Power Supply
11.2 - 12.5VDC. Maximum output current: 0.25A x Number of installed FPS1000 units.
Output Voltage Trimming
Possible. Refer to instruction manual.
AC Input Connector
FPS-S1U: IEC inlet for each power supply module. FPS-S1U/P: None
Output Terminals
Bus-bars. Refer to outline drawing.
Number of Power Supply Modules (*5)
Maximum 3 FPS1000 modules of the same output voltage rating.
Environment
Operating Temperature
℃
0 to 50: 100% load. Derate 2%/
℃
, 50 to 60.
Storage Temperature
℃
-30 to 85
Operating Humidity
%
RH
10 - 90, no condensation.
Storage Humidity
%
RH
10 - 95, no condensation.
Vibration
Built to meet ETS 300 019
Shock
Built to meet ETS 300 019
Isolation
Withstand Voltage
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground: 500Vrms, 1min.
Isolation Resistance
More than 100M
Ω
at 25
℃
and 70% RH. Output-Ground: 500VDC
Standards Safety Standards
UL60950-1, EN60950-1, CSA C22.2 No.60950-1
Mechanical
Weight (typ)
g
3700
Size (W x H x D)
mm
440 x 44 x 351 (Refer to outline drawing.)
(*1) For input voltage lower than 100VAC, maximum output power is 2700W.
(*2) For cases where conformance to various safety standards (UL, EN etc.) is required, to be described as 100-240VAC (50/60Hz).
(*3) Remote sensing can compensate up to 1V drop on each load wire.
(*4) Not applicable for units with I
2
C bus option.
(*5) The output of all the FPS1000 modules are connected in parallel in the rack.
(*6) Up to 3 racks with max.8 FPS1000 units of the same voltage and current rating.
FPS-S1U Specifications
FPS
-S1U