FPS

A-48

Fig.1 Rated output current vs rated output voltage

V2

Vout (V)

V1

l1

l2

   

FPS1000

-24

 

V1

V1

Model

 

24V  

V2

29V  

l1

 

33A  

l2

 

40A

FPS1000

-12

12V

13.2V

66A
72A

 

48V
58V

17.25A

21A

FPS1000

-48

Iout (A)

・All specifications are subject to change without notice.

ITEMS/UNITS

MODEL

FPS1000-12

FPS1000-24

FPS1000-48

Input

Voltage Range 

(*1)

V

AC85 - 265 continuous (Universal input)

Frequency 

(*1) Hz

47 - 63, single phase

Power Factor (115/230VAC) (typ)

More than 0.98 at maximum output power

Efficiency (typ) 

(*2)

81 / 83

84 / 86

85 / 88

Current (100/200VAC) (max)

A

12.0 / 6.0

Inrush Current 

(*3)

A

Less than 40

Leakage Current (230VAC)

mA

Less than 1.1

Output

Nominal Voltage

VDC

12

24

48

Maximum Current 

(*Fig.1)

A

72

40

21

Maximum Power

W

864

960

1008

Voltage Set Point

12V +/-1%

24V +/-1%

48V +/-1%

Maximum Line Regulation (*5)

0.40%

Maximum Load Regulation (*6)

0.80%

Temperature Coefficient

200PPM/

Warm Up Drift

0.1% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temperature.

Maximum Ripple & Noise  (*4) mVp-p

150

200

300

Hold-up Time (100VAC)(typ)

ms

20 at rated output voltage and less than 80% of rated load.

Voltage Adjustable Range

VDC

10.5 - 13.2

21.5 - 29

43 - 58

Function

Over Current Protection (*Fig.1)

105 - 125% of maximum output current.

Over Voltage Protection  (*8) VDC

14.3 - 15.7

31 - 34

62 - 66

Over Temperature Protection

Inverter shut down method, automatic reset.

Remote Sensing 

(*7)

Possible. Refer to instruction manual.

Remote ON/OFF Control

By electrical signal or dry contact. ON: 0 - 0.6V or short.  OFF: 2 - 15V or open.

Parallel Operation 

(*9)

Possible. Refer to instruction manual.

Series Operation 

(*10)

Possible. Refer to instruction manual.

Over Temperature Alarm Signal

Open collector signal. Normal: ON, Max.sink current: 10mA.

DC OK signal

Open collector signal. On when Vout>80+/-5% rated output.  Max.sink current: 10mA

AC Fail Signal

Open collector signal. On when Vin > 85VAC, Max.sink current: 10mA.

AUX-BIAS Power Supply

11.2 - 12.5VDC. 0.25A maximum output current.

Output Voltage Trimming

Possible, via Vout trim pin in the I/O connector. Refer to instruction manual.

Front Panel Indicators

AC OK, DC OK,  DC FAIL

I²C Interface

Optional. Refer to instruction manual.

Environment

Operating Temperature

0 to 50: 100% load. Derate 2%/

, 50 to 60

Storage Temperature

-30 to 85

Operating Humidity

RH

10 - 90, no condensation.

Storage Humidity

RH

10 - 95, no condensation.

Vibration

Built to meet ETS 300 019

Shock

Built to meet ETS 300 019

Cooling

By internal fans. Variable speed control.

Isolation

Withstand Voltage

Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground: 500Vrms, 1min.

Isolation Resistance

More than 100Mohm at 25

 and 70% RH. Output-Ground: 500VDC

Standards

Safety Standards

Approved by UL60950-1, EN60950-1, CSA C22.2 No.60950-1

EMI 

(*11)

EN55022B, FCC part 15J-B, VCCI-B

Mechanical

Weight (typ)

g

2000

Size (W x H x D)

mm

127 x 41 x 290 (Refer to outline drawing.)

  (*1) For cases where conformance to various safety standards (UL, EN etc.)
 

is required, to be described as 100-240Vac (50/60Hz).

  (*2) At 100/200VAC, rated load and 25

 ambient temperature.

  (*3) Not applicable for the noise filter inrush current less than 0.2ms.

  (*4) Measured with JEITA RC-9131 1:1 probe, 20MHz B.W.

  (*5) From 85-132Vac or 170-265VAC, constant load.

  (*6) From no-load to rated load, constant input voltage.

 

Measured at the sensing point in remote sense.

  (*7) Remote sensing can compensate up to 1V drop on
 

each load wire.

  (*8) Inverter shut down method. Reset by AC voltage
 

recycle or by ON/OFF control.

  (*9) Derate maximum output power by 10% for input
 

voltage less than 100V

RMS

.

  (*10) Series operation is not applicable for units
 

with I

2

C bus option (/S, /PS model).

  (*11) For FPS 1000-12/P(S), when used not with FPS-S1U or FPS-T1U

 

racks, an EMI suppressor clamp should be attached to the AC cable,

 

as close as possible to the AC inlet, to meet class B.

FPS1000 Specifications

FPS

1000