EZA2500 Series
TDK-Lambda
<Page>
9-1-5.
Charge/Discharge Conversion Command, CHRG
Charge/Discharge Conversion Command, CHRG (Pin 9) is used for operation mode change.
The converter change to the Charging mode when this signal is open.
The converter change to the Discharging mode when this signal short to SG.
There is behavior differs on operating mode and DIP switch setting. Please refer to
6
8-3.
DIP SW
7
.
9-1-6.
Alarm Clear Command, ALM CLR
During converter stoppage due to alarm, the latched alarm of this converter can be reset by Alarm Clear Command
ALMCLR (Pin 11) short to SG, then open again.
9-1-7.
Service Power Supply, AUX 5V
Service Power Supply (Pin 15) is referenced to SG with approximately 4.7V.
A maximum of 20mA DC load can be connected. Current limit should be provided externally outside the converter.
*SG(Signal Ground) is functional insulation from converter ground.
12/22
PIN #
I/O
Signal
Signal Operation
Response time
Internal Circuit
External Condition Example Circuit
Note
1
O
ALM
Open at Heavy Alarm
-
Extra Circuit
Voltage:
5V
I
30V
(max 20mA)
Open Drain Output.
Current Limitation shoud ve limited by External
Circuit.
Pin #1 becomes opend whien heavy alarm occurs.
3
O
PG
Short at Operating
-
Extra Circuit
Voltage:
5V
I
30V
(max 20mA)
Open Drain Output.
Current Limitation shoud ve limited by External
Circuit.
Pin #3 becomes short to SG when converter
operating.
5
I
STOP
Converter Shut Down at Falling
Edge Input
2ms(typ.)
+Chattering
removal time
(16ms)
No Voltage
Contact Input
When use semiconductor SW, ON voltage should be
0.3V maximum.
Converter can be forcibly stopped by pin #5 short to
SG.
Converter shuts down is by falling edge of input signal
and is hold if input signal released.
7
I
RUN
Conversion is Started at
Falling Edge Input
Conversion is Stopped at
Rising Edge Input
10ms(typ.)
30ms(max)
+Chattering
removal time
(60ms)
No Voltage
Contact Input
When use semiconductor SW, ON voltage should be
0.3V maximum.
Converter starts operate by pin #7 short to SG.
Converter will be started operate by falling edge of
signal and keep operate under low level signal.
Converter will be stopped by rising edge of input signal
released.
9
I
CHRG
Chrging mode at Short input
10ms(typ.)
30ms(max)
+Chattering
removal time
(60ms)
No Voltage
Contact Input
When use semiconductor SW, ON voltage should be
0.3V maximum.
This signal used in combination with RUN signal.
At Manual CV Mode
Power conversion is between Generation and
Regeneration. Generate operation when pin#9 short to
SG. Regeneration mode when pin#9 open.
At Automatic Grid CV Mode
Power conversion is between Manual Grid Mode and
Automatic Grid Mode. Manual Grid Mode when pin#9
short to SG. Automatic Grid Mode when pin#9 open.
This command does not function at Automatic Battery
Mode.
11
I
ALMCLR
Alarm Clear at Falling Edge
10ms(typ.)
30ms(max)
+Chattering
removal time
(60ms)
No Voltage
Contact Input
When use semiconductor SW, ON voltage should be
0.3V maximum.
During converter stopped due to ALM, converter can
be restart by ALMCLR.
Become alarm clear by pin #11 short to SG, then open
again.
13
I
Reserved
-
-
-
No Voltage Contact Input
-
Reserved. Do not connect.
15
-
AUX5V
-
-
-
-
Current limitation should be limited by External Circuit.
SG
24V
4.7K
LED
SG
24V
4.7K
LED
SW
SW
SW
SW
H
L
NO Alarm
Alarm
H
L
Operate
H
L
H
L
ON
OFF
OFF
H
L
Discharge
Charge
SG
ALM
15
15
. ,0 x
1SS388
SG
PG
15
15
. ,0 x
1SS388
SG
STOP
10k
. ,/ x
1SS388
330
F5V
. ,/ x
SG
RUN
10k
. ,/ x
1SS388
330
F5V
. ,/ x
SG
CHRG
10k
. ,/ x
1SS388
330
F5V
. ,/ x
SG
ALMCLR
10k
. ,/ x
1SS388
330
F5V
. ,/ x
F5V
RB521SM-40
AUX5V
SG
H
L