5-2. Output Derating 

      Make sure that the specified temperature range is maintained.  
 

Convection cooling

             

MODEL: CUS150M1-12, CUS150M1-18, CUS150M1-24, CUS150M1-36, CUS150M1-48 

Ta (°C) 

MOUNTING A,B,E 

MOUNTING C 

MOUNTING D 

LOAD (%) 

LOAD (%) 

LOAD (%) 

-20 - +40 

100 

100 

100 

50 100 

100 

75 

60 75 

70 

50 

65 63 

55 

38 

70 50 

40 

25 

 

 

 

5-3. Mounting Method

 

Insert the spacer (Max

φ

7mm) of height more than 8mm to lift the unit. And use all mounting holes for the unit installation. The vibration 

spec is specified under this mounting condition. Keep enough space in the power supply surroundings and the upper area of components for 
convection cooling 

 

(1)

 

Mounting Holes size:  4 holes

φ

3.5mm.               

Содержание CUS150M1 Series

Страница 1: ...plications which require very high reliability Nuclear related equipment medical equipment traffic control equipment etc it is necessary to provide a fail safe mechanism in the end equipment Do not in...

Страница 2: ...nation Mountinghole holediameter 3 5mm Thisholeis notconnectedto ProtectiveEarth of CN1 L ACInputterminalLiveline Fuse inline N AC Input terminal Neutralline Fuse inline Earthterminal Mounting hole ho...

Страница 3: ...50M1 4 2 Output Voltage Range Output voltage is set the rated value at shipment V ADJ trimmer VR51 can adjust the output voltage within the range Output voltage range refers to the specification To tu...

Страница 4: ...er ripple will becomes larger In this case electrolytic capacitor film capacitor etc might be necessary to use across the load terminal The output ripple cannot be measured accurately if the probe gro...

Страница 5: ...set current limit of the withstand voltage test equipment to 20mA The applied voltage must be gradually increased from zero to the testing value and then gradually decreased for shut down When timer i...

Страница 6: ...MOUNTING D LOAD LOAD LOAD 20 40 100 100 100 50 100 100 75 60 75 70 50 65 63 55 38 70 50 40 25 5 3 Mounting Method Insert the spacer Max 7mm of height more than 8mm to lift the unit And use all mountin...

Страница 7: ...ry from the solder surface If the space is not enough the specification of isolation or withstanding voltage will not be satisfied 3 Protective Earth should be connected to the earth terminal of the e...

Страница 8: ...ncluding that the unit is at fault 1 Check if the rated input voltage is connected 2 Check if the wiring of input and output is correct 3 Check if the wire thickness is enough 4 Check if the output cu...

Отзывы: