background image

HANDBOOK FOR CPFE500F SERIES                   

61006

Issue2

Page 2

CONNECTION DETAILS

Input Connection

Mains input connection by 3way AMP 'Mate-n-lock' connector
Mating 3-way housing: AMP 350766-1.
Mating crimp terminals: AMP 926893-1 (14~20AWG), 926895-1 (18~24AWG)

Pin 3 : Live
Pin 2 : Earth
Pin 1 : Neutral

Internal Fuse Type: F15AH 250V

Output Power Connection

DC ve & -ve connection by two M6x18 studs, max torque 10Nm.

Use appropriate ring terminals and wire for the load and short circuit current.

Output Signals

Signal connections available on two 10-way 2.5mm header connectors (ref J2,J3).
Mating 10-way housing : Molex 22-01-1103.
Mating crimp terminals : 08-50-0032 (22~30AWG)
Pinout :-

J2,J3 Pin

Function

1

+ Sense

2

- Sense

3

COM

4

- remote on/off

5

+ remote on/off

6

Aux

7

Current share

8

Trim

9

ENA

10

IOG

Safety Approvals

UL/CSA 60950-1, IEC/EN60950-1

Intended for installation in a non-operator access environment
Intended for installation in an external electrical/mechanical fire enclosure.

EMC & IMMUNITY

Conducted Emissions - EN55022 Class B

Radiated Emissions - EN55022 Class B  

(Note 5)

Immunity - EN61000-4-2, -3, -4, -5, -6, -8, -11

(Note

 

5) see application note for curve B

FAULT FINDING

If the unit shuts down, switch off or remove the supply as it could be that an over voltage or
over temperature condition has occurred. In the event of an over temperature condition,
ensure the unit has cooled down before re-applying the supply.
If the unit still fails to power up, return to TDK-Lambda UK Ltd for investigation and repair.

MECHANICAL DIMENSIONS

Base Plate

temperature

Measurement

point