CME-2

CME

All specifications are subject to change without notice.

MODEL

ITEMS/UNITS 

CME150-24

CME240P-24

Input

Voltage Range 

(*3)

V

AC85 - 265

Frequency 

(*3)

Hz

47-63

Power Factor (100/200VAC)(Typ) (*2)

0.99 / 0.95

Efficiency (Typ)  

(*2)

%

82

80

Current (100/200VAC)(Typ) (*2) A

2.0 / 1.0

3. 2/ 1.6

Inrush Current (100/200VAC)(Typ) (*4) A

14 at 100VAC, 28 at 200VAC, Ta=25

°C

, Cold Start

Leakage Current (265VAC)  (*10) mA

Less than 0.3

Less than 0.22

Output

Nominal Voltage 

VDC

24

Maximum Current 

A

6.3

10

Maximum Peak Current  (*1) A

7.5

20

Maximum Power 

W

151.2

240

Maximum Peak Power 

(*1)

W

180

480

Maximum Line Regulation (*5,*6) mV

96

Maximum Load Regulation (*5,*7) mV

150

192

Temperature Coefficient 

Less than 0.02% / 

°C

Maximum Ripple & Noise 0<Ta<60

°C

 (*5) mVp-p

150

240

Maximum Ripple & Noise -10<Ta<0

°C

 (*5) mVp-p

180

360

Hold-up Time (Typ) 

(*2)

ms

20

Voltage Adjustable Range  (*10) VDC

21.6-26.4

21.6-28.8

Function

Over Current Protection  (*8) A

7.87 -

20.5 -

Over Voltage Protection  (*9) VDC

27.6 - 32.4

30.0 - 35.0

Remote ON/OFF Control  

-

Parallel  Operation 

-

Series Operation 

Possible

Environment

Operating Temperature  (*11)

°C

-10 to +60

°C

(-10 to +50°C:100%, +60°C:80%)

-10 to +60

°C

(-10 to +45°C:100%, +60°C:60%)

Storage Temperature 

°C

-30 to +85

°C

Operating Humidity 

%RH

30 - 90 (No dewdrop)

Storage Humidity 

%RH

10 - 95 (No dewdrop)

Vibration 

At no operating, 10-55Hz (Sweep for 1min.) 

19.6m/s² Constant, X,Y,Z 1hour each

Shock (In package) 

Less than 196.1m/s²

Cooling 

Convection Cooling

Isolation

Withstand Voltage 

Input - FG : 2kVAC (20mA), Input - Output : 4kVAC (20mA) 

Output - FG : 500VAC (100mA) for 1min.

Isolation Resistance 

More than 100MΩ at 25

°C

 and 70%RH, Output - FG : 500VDC

Standards

Safety Standards 

(*12)

Approved by UL60601-1,EN60601-1 

Built to meet UL60950-1,CSA60950-1,EN60950-1, and DENAN

PFHC 

Built to meet EN61000-3-2 

EMI 

(*13)

Built to meet EN55011 / EN55022-B, FCC-ClassB, VCCI-B

Immunity 

Built to meet EN61000-4-2, -3, -4, -5, -6, -8, -11

Mechanical

Weight (Typ.) 

g

500

800

Size (W×H×D) 

mm 80 x 40 x 208 (Refer to Outline Drawing) 105 x 50 x 242 (Refer to Outline Drawing)

Specifications

*Read instruction manual carefully, before using the power supply unit.
  (*1) Operating period at peak output current is less than 10sec.
 

 Input voltage < 95V : Duty < 0.2

 

 Input voltage > 95V : Duty < 0.35

 

 (Average output power and current is less than Maximum output power and current)

 

 For peak load derating method, please refer to the instruction manual for details.

  (*2) At 100/200VAC, Ta=25°C and maximum output power.
  (*3) For cases where conformance to various safety specs (UL,CSA,EN) are required, to be described as100 - 240VAC, 50/60Hz on name plate.
  (*4) Not applicable for the in-rush current to Noise Filter for less than 0.2ms.
  (*5) Please refer to Fig. A for measurement of line & load regulation and ripple voltage.(Measure with JEITA RC-9131 probe) 
  (*6) 85 - 265VAC , constant load.
  (*7) No load - Full load (maximum power), constant input voltage. 
  (*8) Constant current limit and hiccup with automatic recovery. Avoid to operate at overload or dead short condition for more than 30 seconds.
  (*9) OVP circuit will shut down output, manual reset.(Line recycle)
 (*10) Measured by the each measuring method of IEC, UL, CSA, EN and DENAN(at 63Hz). 
 (*11) At standard mounting. 
 

 - Load (%) is percent of maximum output power or maximum output current, whichever is greater.

 

 - For other mountings, refer to derating curve.

 (*12) As for DENAN, built to meet at 100VAC.
 (*13) No load - Full load (maximum power), constant current and input voltage.

Содержание CME Series

Страница 1: ...E240P 24 Output voltage 24V 24V Max output current 6 3A 10A Max output power 151 2W 240W Peak output current 7 5A 20A Peak output Power 180W 480W UL60601 1 CSA 22 2 No 601 1 M90 cUL certified EN60601...

Страница 2: ...Standards Safety Standards 12 Approved by UL60601 1 EN60601 1 Built to meet UL60950 1 CSA60950 1 EN60950 1 and DENAN PFHC Built to meet EN61000 3 2 EMI 13 Built to meet EN55011 EN55022 B FCC ClassB VC...

Страница 3: ...1 1 J S T 9 11 HAND CRIMPING TOOL YC 160R MANUFACTURER J S T 37 1 80 1 70 0 5 Ground the FG to the safety ground of the equipment or device There must be at least 4 mm gap between the end of the print...

Страница 4: ...romagnetic field erosive gas etc or any environment where conductive foreign substance may enter Do not operate and store this unit at the condition of condensation In such case waterproof treatment i...

Страница 5: ...EN60601 1 2 EMC but EMC test data is available from TDK LAMBDA Corporation Special Instructions for IEC EN UL 60601 1 1 Terminal Explanation CME150 CME240P 1 L AC input terminal pin 1 of CN1 Live lin...

Страница 6: ...erload or dead short conditions for more than 30 seconds which could result in damage or insulation failure Output Ripple Noise The standard specification for maximum ripple value is mea sured accordi...

Страница 7: ...ge load after derating by vari ous Mounting and Ta Examples of peak load derating calculated by above formula Actual Io Average Load Io A Ip A max D max Im A Io A 100 10 20 35 0 3 92 9 55 90 9 20 30 4...

Страница 8: ...lso use all 4 mounting holes for the unit installation The vibration spec is the value taken when the unit is raised by 8mm spacers And allowable area by metal pieces is 9mm from each PCB corners Refe...

Страница 9: ...igh braking capac ity fuse when selecting the external fuses that are to be used on input line Surge current flows when line turns on There fore use slow blow fuse or time lug fuse Do not use fast blo...

Страница 10: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information TDK Lambda CME240P 24...

Отзывы: