MA00001E00 V_1.1
9
Name
Description
Min
Max
Default
Notes
L.00
slave address to query
0
247
1
0
→
BUS IDLE
L.01 bitrate 0
3
0
0 = 19.2kbps, 1 = 38.4kbps, 2=
57.6kbps, 3 = 115.2kbps
L.02
save to NVM
0
1
0
(1)
L.03
reload from NVM
0
1
0
(1)
L.04 load
defaults 0
1
0
(1)
L.05
setup for drive 2nd RS485
interface
0 1 0
(1)
equal to set L.00 = 1, L.01 = 1
Notes: (1) – parameter value auto reverts to 0 and is not saved to NVM
9.4 MENU FLB (FIELDBUS PARAMETERS)
FLB menu refers to parameters related to Fieldbuses management that was previusly accessible only by
OPD Explorer as they weren't associated to any “standard” parameter, connection or extra parameter and so
not accessible by keypad. Now they are grouped in this new menu, as listes in following tables, and so they
can be viewed and changed (if not read-only) by keypad.
As there are no format tables for these parameter, an abitrary format was assigned to each parameter based
on the use/meaning. For many of them, also, a HEX a decimal representation was choosed to show and edit
raw 16bit data value.
Notice that all parameters in FLB menu are not protected by any key nor by run status so they can be
changed at any time. Also, be aware that some parameter related to the configuration of fieldbuses take
effect only at power on so changes become effective only after saving and cycling the power supply.
Parameters related to configuration of Profibus DP and Anybus CC
Name
OPD Explorer name
OPD Explorer
description
Min
Max
Default
UM
F.00 NODE_SLAVE_ADDR
Slave
address
0
255
0
F.01 NODE_BAUD_RATE
Node
baudrate
0000 FFFF 0000 HEX
F.02
DATA_CONSISTANCE
Data
consistance 0 1 0
F.03
EN_ACYCLIC_DATA
Enable acyclic data
0
1
1
F.04 EN_BIG_ENDIAN
Most significant bytes in
multi-byte data types
0 1 1
F.05 PDP_SETUP_DATA
Old Profibus DP setup
data
0000 FFFF 0000 HEX
F.06
FLDB_ERROR_CODE
Fieldbus error code
0000
FFFF
(1)
HEX
F.07 FLDB_STATE
Fieldbus
state 0000
FFFF
(1)
HEX
Notes: (1) - read only
Parameters related to configuration of Anybus CC only
Name
OPD Explorer name
OPD Explorer description
Min
Max
Default
UM
F.08
IP_ADDR_00
Anybus IP Address 00
0
255
192
F.09
IP_ADDR_01
Anybus IP Address 01
0
255
168
F.10
IP_ADDR_02
Anybus IP Address 02
0
255
0