5. Configuration
The device can be configured via DIP switches and jumpers manually or with the
corresponding software “Digalox Manager” via USB interface. When configuring via
DIP switches and jumpers the basic settings can be made computer-independent.
The configuration with the software “Digalox Manager” allows full functionality.
Scaling
In modes where a scaling is necessary to represent the correct measurement value
(for example 5 A AC for current transformer) the upper scale value corresponds to
the primary value of the current transformer or shunt.
Example:
upper scale value = 50 = primary value of the current transformer
Configuration via USB interface with software “Digalox Manager”
For configuration with software set DIP switch 10 to OFF position.
Please note that the measurement mode selected in "Digalox Manager" is displayed
only until the power supply of the DPM72 is interrupted.
In further operation, the device always shows the measurement mode,
which is selected by the jumpers J4-J6 or the DIP switches 11-12
respectively!
(see table "Measurement mode").
Configuration via DIP switches and jumpers if only one measurement mode is
required (Manual mode)
1. Set DIP switch 10 to ON position.
2. Set measurement mode with jumpers at J4-J6 according to table "Measurement
mode”, column “Manual mode".
3. Set upper scale caption for the first measurement mode with DIP switches 1-9
(see “Configuration of the upper scale caption”).
4. Connect supply voltage.
-----
4
-----