Introduction

Congratulations on choosing the TCS QD2040b! The QD2040b is a compact, versatile network controller that seamlessly 

connects with the Ubiquity Cloud™ via TCSbus or Modbus.
This manual includes all the information you will need to properly install and set up your QD2040b. As most units come 

preconfigured, you will most likely only need to read the Installation section of this manual and you can skip the Configura

-

tion section. However, some customers do order their units without being configured beforehand; for those customers, we 

include the comprehensive Configuration section which contains essential information they will need to set up the unit.
If you have any questions regarding your QD2040b or your network, do not hesitate to contact TCS Technical Support at 

800-288-9383, ext. 2.

Material List

•  QD2040b Ubiquity Cloud Site Gateway 
•  External Power Supply
•  Wall Mounting Bracket

Mounting

The QD2040b is designed to be hung on a wall via the mounting screw holes in each unit. It may also be set on a shelf or 

table. 

Do not allow the mounting screws to touch the circuit board inside the enclosure

.

When selecting a location to mount the QD2040b, be sure to allow space for cable connections. Locate the QD2040b 

away from excessive dust, heat sources, moisture or direct sunlight. The ideal environment is a server room. The tempera-

ture of the room should not exceed 77ºF (25ºC); good ventilation is mandatory.

Input Connections

Refer to the "QD2040b Power and Communication Connections Diagram" on page 4 for the following input connec-

tions:

Power: 

Attach the included power supply to the back of the QD2040b and insert the power plug into a 120 VAC socket. 

Upon connection the unit should power up automatically If it does not, press the Power button once. 
Ethernet: Connect an Ethernet cable to the Ethernet LAN outlet. If you are using a cellular modem, connect the Ethernet 

cable to the Ethernet port on the Cellular Modem.

RS-485 Network: 

Connect an RS-485 network to one of the COM ports. 

USB PORT 1-4 (Optional)

: Connect an RS-485 network via a USB cable to an RS-485 converter (QD1010), or connect a TCS 

ZigBee network via a wireless gateway (QW1010). 

NOTE:

 The remaining connections on the QD2040b are unused and should not be plugged in.

Содержание Ubiquity QD2040b

Страница 1: ...WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com v 2105 Installation Manual The QD2040b Ubiquity Cloud Site Gateway connects the site controller network with the Ubiquity Cloud server QD2040b U...

Страница 2: ...ht Up 7 No Communications with Controllers on the Network 7 No LAN Link to the Internet 7 No Communication with RS 485 Ports COM 1 and 2 Ubiquity Time out or No Data 8 Configuration 9 Gateway Configur...

Страница 3: ...to be hung on a wall via the mounting screw holes in each unit It may also be set on a shelf or table Do not allow the mounting screws to touch the circuit board inside the enclosure When selecting a...

Страница 4: ...er is reached Wiring is such that all A wires are connected to A wires all B wires are connected to B wires and all REF wires are connected to REF wires NOTE A refers to the negative RS 485 connection...

Страница 5: ...hielded twisted three conductor com munications wiring with one end earth grounded 120 balancing resistors provided Shielded twisted three conductor com munications wiring with one end earth grounded...

Страница 6: ...NOTES 1 If using more than 64 controllers use the second RS 485 port or additional QD1010 adapters 2 Each controller must use the same baud rate and be assigned a unique address Two Wire Network Wiri...

Страница 7: ...trollers on the Network Make sure the baud rate selection for the QD2040b is set to match the baud rate of all the controllers on each port net work the default communication speed of the serial bus i...

Страница 8: ...Each port is also optically isolated which cleans up the signal and also protects the unit from taking stray voltage off the RS 485 lines A set of LEDs on each of the RS 485 ports on the QD2040b allo...

Страница 9: ...proper parameters for your application If you are unable to access the configuration page contact TCS Technical Support 800 288 9383 ext 2 for assis tance All Ubiquity Cloud services are accessed by...

Страница 10: ...ta to the Ubiquity Cloud Server Application Options You must select a Network Polling Cycle Time for the QD2040b This is the time interval that the unit will poll the entire network of controllers on...

Страница 11: ...r SSL requires port 443 to be open Protocol Select the communications protocol being used on each port TCSbus is selected by default Baud Rate This is the data transmission speed on the network The Ba...

Страница 12: ...ddress settings are automatically assigned when communication is established MTU Adjustments Adjusting the MTU down may allow gateways to communicate with smaller TCP packet sizes This may be useful i...

Страница 13: ...asys com 13 Configuration Security Information Commissioning Tools You can access a separate page containing various commissioning tools by clicking the Commissioning Tools button at the bottom of the...

Страница 14: ...rror No Route to Host The unit does not currently have an Ethernet connection 2 Connected The unit is able to communicate to the Ubiquity Cloud Server BUT is not being matched up with a spe cific site...

Страница 15: ...n Once the update has been downloaded it is automatically applied and the unit will reboot if necessary NOTE The Check for Update command requires that the QD2040b have Internet access to retrieve the...

Страница 16: ...ne Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 16 2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 16 Configuration Gateway Configuration Applica...

Страница 17: ...ne Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 17 2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 17 Configuration Proxy Options Extended Applic...

Страница 18: ...o VGA cable 3 USB Keyboard Connection Setup Monitor and Cable Connect the cable to the monitor to the QD2040b matching up the corresponding ends HDMI VGA Power on the moni tor and switch to the proper...

Отзывы: