background image

2800 Laura Lane • Madison, WI 53562  |  800.288.9383 • fax: 608.836.9044  |  www.tcsbasys.com  

4

5

All controls connected to the network will need to be programmed with the same communication baud rate as well as 

a unique communication address from 0 to 255, excluding 248 . On controllers with displays, this can either be done 

from the face of the controller using the keypad and display, or using TCS Insight software, or by calling TCS Technical 

Support . TCS Technical Support can access the QD2040b online and change the address of a controller . 
Use 22 AWG, twisted shielded 3-conductor cable for network wiring . Network wiring should start at one controller and 

go to the next and then go to the next, and so on until the final controller is reached . Wiring is such that all “A” wires are 

connected to “A” wires, all “B” wires are connected to “B” wires, and all “REF” wires are connected to “REF” wires . 

A 120 Ω terminating resistor should be placed at each of the two ends of the network directly across the “A” and “B” 

wires. If the QD2040b will be at one end of the network, hard wired a 120 Ω terminating resistor across the “A” and “B” 

terminals at the QD2040b (See 1 below) .
If the QD2040b will be in the middle of the network, do not wire in the terminating resistor on the QD2040b terminal 

block (See 2 below) . Finally, connect one end (ideally the furthest end from the QD2040b) of the shield wire of the 

network wiring to earth ground . TCS recommends a 250 milliseconds time out period for all wired networks, and 1000 

milliseconds for wireless networks . If you encounter timeout errors please contact tech support . 

NOTE:

 In the middle of the network, all network wiring shields should be twisted together and taped off to prevent 

accidental grounding . More than one ground on the network wiring can result in communication failure .

NOTE:

 A maximum of 2 terminating resistors can be used . See Figure below . 

NETWORK 

WIRING & SETUP

RS485 Controller Network Wiring and Setup

A
B

REF

Shield

A
B

REF

A
B

REF

Earth Ground

Only at one end

Drain

Wire

Last in Daisy Chain

120

 

Terminating

Resistor

...

COM 1

COM 2

REF

REF

A

A

B

B

USB PORT 2

USB PORT 1

ETHERNET

USB PORT 3

USB PORT 4

VIDEO

AUX VIDEO

Drain

Wire

...

120

 

Terminating

Resistor

A
B
REF

A
B
REF

A
B
REF

.

.

.

Last in Daisy Chain

Shield

Last in Daisy Chain

Earth Ground

Only at one end

120

 

Terminating

Resistor

A
B
REF

A
B
REF

A
B
REF

Shield

Drain

Wire

COM 1

COM 2

REF

REF

A

A

B

B

USB PORT 2

USB PORT 1

ETHERNET

USB PORT 3

USB PORT 4

VIDEO

AUX VIDEO

120

 

Terminating

Resistor

1

2

3

3

4

4

4

1

3

2

4

QD2040b in the middle of the network

Shielded, twisted 3-conductor communications wiring 

with one end earth grounded. (120 

 balancing 

resistors provided.)

Shielded, twisted 

3-conductor 

communications wiring 

with one end earth 

grounded. (120 

 

balancing resistors 

provided.)

NOTES:

1 . 

If using more than 64 

controllers, use the second 

RS-485 port or additional 

QD1010 adapters. 

2 . 

Each controller must use 

the same baud rate and be 

assigned a unique address. 

QD2040b in the end of the network

Содержание Ubiquity QD2040b

Страница 1: ...WI 53562 800 836 9044 fax 608 836 9044 www tcsbasys com Rev 0617 The QD2040b Ubiquity Cloud Site Gateway connects the site controller network with the Ubiquity Cloud server QD2040b Ubiquity Cloud Site...

Страница 2: ...tines Supervisory override strategy Auto discovery of networked controllers Two integrated RS 485 serial ports Additional serial ports can be added via USB ports Integrated Ethernet controller with fi...

Страница 3: ...er QD1010 or connect a TCS ZigBee network via a wireless gateway QW1010 Refer to RS 485 Controller Network Wiring Setup below Power Attach the included power supply to the back unit and insert the pow...

Страница 4: ...wiring to earth ground TCS recommends a 250 milliseconds time out period for all wired networks and 1000 milliseconds for wireless networks If you encounter timeout errors please contact tech support...

Страница 5: ...a to the actual server Application Options You must select a Network Polling Cycle Time for the QD2040b This is the time interval that the unit will poll the entire network of controllers on all ports...

Страница 6: ...o be used When using static IP it is necessary to enter the IP Address Gateway Subnet DNS1 and DNS2 settings Virtual IP can be used typically left blank The IP settings will need to be established by...

Страница 7: ...ser interface at this point Clicking the green button with the arrow on it on the right side of the Ubiquity Connection Status title bar will refresh the connection status COMMISSIONING TOOLS Commissi...

Страница 8: ...the network must have a unique address excluding the reserved address 248 Network wiring should also be checked The LEDs on the QD2040b indicate the current operating status of the QD2040b POWER This...

Отзывы: