Configuration
COOL STAGE 2
DIFF: 01F
STEP 10 Cool Stage 2 Differential:
Enter a differential value for cool
stage 2.
NOTE:
This screen appears only if cool stage 2 is enabled
(Step 2).
COOL STAGE 1
DIFF: 01F
STEP 8 Cool Stage 1 Differential:
Enter a differential value for cool
stage 1.
ENABLE OUTDOOR
AIR FUNCT.?
YES
STEP 12 Outdoor Air Sensor Function:
Select whether you are using
an outdoor air sensor for control. If monitoring only, select
NO.
NOTE:
Refer to
SuperSTAT 1041 Installation Manual
for dip
switch settings, which must also be set.
COOL STAGE 1
OFFSET: 00F
STEP 7 Cool Stage 1 Offset:
Enter an offset value for cool stage 1.
(Heat stage 1 is normally 0° offset).
SET CONTROL
MODE P
STEP 11 Control Mode: For configuring staged outputs, select whether
to control by temperature only (P) or include a time factor
(P+I).
COOL STAGE 2
OFFSET: 00F
STEP 9 Cool Stage 2 Offset: Enter an offset value for cool stage 2.
NOTE:
This screen appears only if cool stage 2 is enabled
(Step 2).
COOLING LOCKOUT
TEMP 065F
STEP 13 Cooling Lockout:
Select an outdoor air cooling lockout
temperature.
NOTE:
This screen appears only if the outdoor air sensing
function is enabled (Step 12).
HEATING LOCKOUT
TEMP 070F
STEP 14 Heating Lockout:
Select an outdoor air heating lockout
temperature.
NOTE:
This screen appears only if the outdoor air sensing
function is enabled (Step 12).
Economizer
STEP 1 Discharge Air Sensor Function:
Select whether you are using a
discharge air sensor for control. If monitoring only, select NO.
NOTE:
Steps 2 – 8 will only appear if you are using a discharge
air sensor. Refer to
SuperSTAT 1041 Installation Manual
for dip
switch settings, which must also be set.
ENABLE DISCHARGE
FUNCT.? YES
OUTDOOR AIR ECON
SETPOINT: 068F
STEP 2 Outdoor Air Economizer:
Select the outdoor air setpoint.