Configuration

SET OVERRIDE
TIME 

180 MINUTES

STEP 14  Override Time: The number of minutes (0 – 255) the 

SuperSTAT will maintain overridden occupied setpoints.

LIMIT SETPOINT
/- 

05F

STEP 13  User Setpoint Limit: 

Enter the amount a user is allowed the 

to adjust the preset occupied setpoints

UNOCCUPIED COOL
SETPOINT: 80F

STEP 12  Unoccupied Cool Setpoint: Set the Unoccupied Mode’s 

cooling setpoint.

OCCUPIED COOL
SETPOINT D: 

75F

STEP 11  Occupied Cool Setpoint D: 

Set the cooling setpoint for this 

occupied period.

Heating/Cooling Stages

STEP 1  Second Stage Heat:

 Select whether the SuperSTAT will control 

a second heating stage. If no second heating stage, select NO.

ENABLE SECOND
STAGE HEAT? 

YES

HEAT STAGE 1
DIFF: 01F

STEP 4  Heat Stage 1 Differential:

 Enter a differential value for heat 

stage 1.

HEAT STAGE 2
OFFSET: 00F

STEP 5  Heat Stage 2 Offset: Enter an offset value for heat stage 2.

 

NOTE: 

This screen appears only if heat stage 2 is enabled 

(Step 1).

HEAT STAGE 1
OFFSET: 00F

STEP 3  Heat Stage 1 Offset:

 Enter an offset value for heat stage 1. 

(Heat stage 1 is normally 0° offset).

ENABLE SECOND
STAGE COOL? 

YES

STEP 2  Second Stage Cool:

 Select whether the SuperSTAT will 

control a second cooling stage. If no second cooling stage, 

select NO.

HEAT STAGE 2
DIFF: 01F

STEP 6  Heat Stage 2 Differential:

 Enter a differential value for heat 

stage 2

 

NOTE: 

This screen appears only if cool stage 2 is enabled 

(Step 2).

Содержание SuperSTAT Series

Страница 1: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com CONFIGURATION GUIDE 202308 Communicating Thermostat SuperSTAT SZ1041...

Страница 2: ...ogramming Keypad Access 4 Navigating Via Keypad 4 Programming Setup Mode 5 Basic Setup 5 System Mode 5 Occupancy Settings 6 Heating Cooling Stages 7 Economizer 8 Digital Inputs 9 Energy Saving 10 Keyp...

Страница 3: ...the device wiring the communications network and connecting other devices to the SuperSTAT Your configuration settings will be uploaded to Ubiquity Cloud the first time you make a connection to the si...

Страница 4: ...times when enabled OVERRIDE Press when OCCUPIED LED is off to restore occupied temperature settings clock setup service status Press to review service screens Keypad service status fan switch system s...

Страница 5: ...UE 07 04 23 9 00 AM 72F ENTER ACCESS CODE 000 If the SuperSTAT has been configured to require an access code to enter Programming Mode this screen will appear see Keypad Access Code on page 10 If you...

Страница 6: ...s occupied period OCCUPIED COOL SETPOINT A 75F STEP 8 Occupied Cool Setpoint A Set the cooling setpoint for this occupied period UNOCCUPIED HEAT SETPOINT 60F STEP 7 Unoccupied Heat Setpoint Set the Un...

Страница 7: ...ct whether the SuperSTAT will control a second heating stage If no second heating stage select NO ENABLE SECOND STAGE HEAT YES HEAT STAGE 1 DIFF 01F STEP 4 Heat Stage 1 Differential Enter a differenti...

Страница 8: ...o control by temperature only P or include a time factor P I COOL STAGE 2 OFFSET 00F STEP 9 Cool Stage 2 Offset Enter an offset value for cool stage 2 NOTE This screen appears only if cool stage 2 is...

Страница 9: ...will direct or reverse acting DSCHARGE AIR ECON SETPOINT 055F STEP 3 Discharge Air Economizer Select the discharge air setpoint DSCHARGE AIR ECON LOW LIMIT 040F STEP 4 Discharge Air Low Limit Select...

Страница 10: ...and Schedule menus NOTE Use dip switch settings to lock out access completely see Programming Keypad Access on page 4 Keypad Access Code STEP 1 Programming Access Select whether an access code is requ...

Страница 11: ...Occupancy Time Periods This screen indicates the day of the week shown is ready for configuring up to four occupancy time periods Press the CLOCK SETUP button on the keypad to advance to the setup scr...

Страница 12: ...ady to be configured Press the CLOCK SETUP button on the keypad to advance to the setup screens for the holiday group ENTER DATES FOR HOLIDAY 2 STEP 8 Holiday Group 2 Dates This screen indicates that...

Страница 13: ...ancy time periods to as many as 12 holidays Enter the two digit month date and duration in days To add additional dates to this group press the OVERRIDE button Press the WARMER button to advance the d...

Отзывы: