Configuration
SET OVERRIDE
TIME
180 MINUTES
STEP 14 Override Time: The number of minutes (0 – 255) the
SuperSTAT will maintain overridden occupied setpoints.
LIMIT SETPOINT
/-
05F
STEP 13 User Setpoint Limit:
Enter the amount a user is allowed the
to adjust the preset occupied setpoints
UNOCCUPIED COOL
SETPOINT: 80F
STEP 12 Unoccupied Cool Setpoint: Set the Unoccupied Mode’s
cooling setpoint.
OCCUPIED COOL
SETPOINT D:
75F
STEP 11 Occupied Cool Setpoint D:
Set the cooling setpoint for this
occupied period.
Heating/Cooling Stages
STEP 1 Second Stage Heat:
Select whether the SuperSTAT will control
a second heating stage. If no second heating stage, select NO.
ENABLE SECOND
STAGE HEAT?
YES
HEAT STAGE 1
DIFF: 01F
STEP 4 Heat Stage 1 Differential:
Enter a differential value for heat
stage 1.
HEAT STAGE 2
OFFSET: 00F
STEP 5 Heat Stage 2 Offset: Enter an offset value for heat stage 2.
NOTE:
This screen appears only if heat stage 2 is enabled
(Step 1).
HEAT STAGE 1
OFFSET: 00F
STEP 3 Heat Stage 1 Offset:
Enter an offset value for heat stage 1.
(Heat stage 1 is normally 0° offset).
ENABLE SECOND
STAGE COOL?
YES
STEP 2 Second Stage Cool:
Select whether the SuperSTAT will
control a second cooling stage. If no second cooling stage,
select NO.
HEAT STAGE 2
DIFF: 01F
STEP 6 Heat Stage 2 Differential:
Enter a differential value for heat
stage 2
NOTE:
This screen appears only if cool stage 2 is enabled
(Step 2).