20 Ohm: 

 

 

max. 160 m distance AS/IS-VS by 0.6 mm diameter 
max. 300 m distance AS/IS-VS by 0.8 mm diameter 

 

AS  front-door station 
VS  power supply and control unit 
IS 

indoor station 

FE 

extended functions

 

 

 
 

Repair 

Error detection and indication 

 

Faults are signalled optically and acoustically: constant fault tone and constant flashing of 
the operation display. When pressing any button, a fault tone sounds again. The optical 
fault indication stays active until the fault is corrected.  
 

fault causes 

display  
fault 
mode 

fault tone 

elimination 
 

a- and P-wire are inter-
changed or short-circuited 

 

 

both 

LEDs  

flash 

 

 

change a- and P-wire or eliminate short-circuit,  
device is in stand-by mode again 

a-wire: not connected or 
not supplied 

 

 

connect the a-wire or check power supply, 
device is in stand-by mode again 

button stucks  
(press longer than 15 sec) 

 

 

remove button at the device or loosen floor push but-
ton, device is in stand-by mode again 

 
 

Exchange an indoor station 

– programme bell buttons 

Basics 

  All devices at theTCS:BUS have got an unique serial number.  

  Programming a bell button means that the serial number of an indoor station is allocat-

ed to the bell button of a front-door station and is stored within the EEPROM of the 
front-door station.  

  Ensure that new the indoor stations is connected to the TCS:BUS and the mains volt-

age is switched on (the operation LED at the power supply and control unit is ON) and 
further, that the access to the flat is granted during the programming. 

  This instruction describes the case that a serial number is allocated to the bell button 

without setting a programming lock. To neutralise a programming lock you need a Ser-
vice Device TCSK-01or the configuration software configo

™. 

a, b hier  
kurzschließen 

Содержание ISW3130

Страница 1: ...TCS T rControlSysteme AG Subject to technical changes E Mail hotline tcsag de www tcsag de PI_ISW3130 uk 2 A Product information Comfort indoor station for hands free talking ISW3130...

Страница 2: ...the upper cover 7 Open the device 7 Installation of extended functions 8 Connect the lines 8 Connection lines 8 Wiring example 9 Connection diagram 2 wire technique 9 Connection diagram 3 wire techniq...

Страница 3: ...separators between heavy and low current lines in shared cable ducts use of standard telecommunication lines e g J Y St Y with 0 8 mm diameter existing lines modernisation with deviating cross sectio...

Страница 4: ...OFF is activated flashes ring tone stopper is deactivated door release automatic or call diversion is activated flashes OFF ring tone stopper is activated door re lease automatic or call diversion is...

Страница 5: ...rs like shown in price list dimensions in mm H 180 x W 100 x D 23 weight 185 g acceptable ambient temperature 5 40 C degree of protection IP30 input current stand by 2 wire operation I a 1 mA 3 wire o...

Страница 6: ...oftware configo flat door floor door and internal call a parallel call can be activated with the Service Device TCSK 01 or configo audio privacy function and automatic call cut OFF after 2 min lower c...

Страница 7: ...from the button to the top floor push button at a E Wiring example see page 9 Snap on the upper cover Set on the upper cover at both adjustment increments of the lower cover 1 Snap on the upper cover...

Страница 8: ...the indoor station with adhesive pads see also product information of each extended function Connecting the lines is implemented in analog to the ISW3030 see product information TRE1 EB 1 Connect the...

Страница 9: ...2015 9 TCS T rControlSysteme AG Subject to technical changes E Mail hotline tcsag de www tcsag de PI_ISW3130 uk 2 A Wiring example Connection diagram 2 wire technique Connection diagram 3 wire techniq...

Страница 10: ...check if it is connected to the a wire of the power supply and control unit Settings Preset times conversation time 2 min flashing period of the green LED if the voice channel is busy after establishi...

Страница 11: ...control key until the required ring tone sounds The ring tone selected last is stored 3 Short press the call OFF button Or If no button is pressed for around 8 sec the device end the ring tone select...

Страница 12: ...x unlimited communication time x reset to factory settings x If the floor door release function in the EEPROM has been activated and the door release automatic function via function key is switched on...

Страница 13: ...other and put it one sided on mass b wire in the power supply optional strand or star formed wiring Table loop resistance cable length in m cable diameter 0 6 mm 0 8 mm loop resistance in 10 1 28 0 7...

Страница 14: ...r not supplied connect the a wire or check power supply device is in stand by mode again button stucks press longer than 15 sec remove button at the device or loosen floor push but ton device is in st...

Страница 15: ...Not necessary if the bell buttons have not been programmed comp product information of the front door station 1 If there sounds a Progsperr tone instead the front door station is equipped with a prog...

Страница 16: ...ecting point for electronic scrap Dispose the parts of the packaging in collecting tanks for cardboard and paper resp plastics Warranty We offer a simplified processing in case of warranty for electri...

Отзывы: